DESCRIPTION

These horizontal end suction pumps feature a flow inducing

propeller and one or two impellers in series. These pumps

are supplied with or without mounting base (except for the

DB-F which requires a mounting base). All pumps are con-

structed with mechanical seals intended for high temperature

operations.
All models are bronze fitted with replaceable bronze wear rings.

APPLICATION

The 2' NPSHR rating of these pumps makes them uniquely

suited to pumping hot water. With 2 feet of static suction head,

the pumps will pump boiling water. Typical applications are on

condensate return and boiler feed systems.
These pumps are also well suited for general pumping service

of benign liquids.

PRELIMINARY INSPECTION
Assure that there is no shipping damage.
Assure that nameplate ratings agree with job specifications and

actual conditions.

PUMP LOCATION
Locate the pump so there is sufficient room for inspection,

maintenance and service. If the use of a hoist or tackle is

needed, allow ample head room.

LOCATION
The best pump location for sound and vibration absorption

is on a concrete floor with sub soil underneath. If the pump

location is overhead, special precautions should be under-

taken to reduce possible sound transmission, consult a sound

specialist.
If the pump is not installed on a closed system, it should be

placed as near as possible to the source of the liquid supply,

and located to permit installation with the fewest number of

bends or elbows in the suction pipe.
The installation must be evaluated to determine that the Net

Positive Suction Head Available (NPSHA) meets or exceeds the

Net Positive Suction Head Required (NPSHR) as stated by the

pump performance curve.

INSTALLATION

This pump is built to provide years of service if installed prop-

erly and attached to a suitable foundation. A base of concrete

weighing 2

1

/

2

times the weight of the pump is recommended.

(Check the shipping ticket for pump weight.)
If possible, tie the concrete pad in with the finished floor. Retain

access to pump mounting screws of DB-F pumps.

To facilitate easy servicing, some type of expansion fitting

should be utilized. The female portion should be inserted into a

suitable hole in the floor so that its top surface is flush with the

floor surface. Thus, when the hold-down bolts are removed,

the motor can be removed by sliding it back from the pump.

(See below.)

WARNING: EXPLOSIBLE

Maximum suction pressure is 35 psi unless otherwise

specified by manufacturer. Do not exceed this pressure.

Failure to follow these instructions could result in serious

injury or death.

CAUTION: NOT A CHEMICAL PUMP

Inject boiler feed compounds from chemical feed tank

into boiler feed piping – never into pump suction. Failure to

follow these instructions could result in injury or property

damage.

WARNING: Eyebolts or lifting lugs if provided are for

lifting only the components to which they are

attached. If lifting of the entire pump is required, do so with

slings placed under the pump assembly as shown. Failure

to follow these instructions could result in injury or death.

FOUNDATION BOLT

PIPE SLEEVE

WASHER

BUILT-UP

CONCRETE FOUNDATION