DESCRIPTION

Pumps ar

e float operated to return accumulated condensate to

a boiler feed tank.

Receivers are non-code cast iron or steel.

PRELIMINAR

Y INSPECTION

Assur

e that there is no shipping damage.

Assure that nameplate ratings agree with job specifications and
actual conditions.

HANDLING
Use car

e in installing unit.

LOCA

TION

Place unit for easy access to all parts. Allow adequate space

for servicing. Check ambient conditions.

NOTICE / TEMPERA

TURE LIMITS

Motors ar

e designed to operate in 104ºF. (40°C) max. ambient.

Insulate or ventilate as required.

PIPING (General)
Pipe the unit per the Elementary Piping Diagram. Locate and

support piping so as to not load the pump discharge.

PIPING (Retur

ns)

Gravity r

eturn lines from system should be properly pitched

down to unit inlet. Returns must also be trapped to pre-
vent steam entry into the unit. An inlet basket strainer is
recommended.

PIPING (V

ent)

Install a vent pipe to atmospher

e. Pipe to be size of vent port

on unit. Do not restrict or reduce vent opening or exceed 20
feet vertical height unless an overflow connection is provided.

PIPING (Overflow)
Pipe overflow port to drain using an overflow loop when con

-

densate temperature will exceed 200ºF. (93°C).

FLOA

T SWITCHES & MECHANICAL ALTERNATORS

Floats ar

e locked in place to prevent damage during shipment.

Remove shipping locks. Check factory settings. Floats and
mechanical alternators are adjustable for various levels of oper-
ation. The lead pump should start with tank

3

/

4

full and shut off

at 2" or more above pump inlet. Lag pump should start before
the tank overflows. Settings should avoid “short cycling” of the
pump.

ELECTRICAL WIRING & CONTROLS
Connect power wiring per NEC. Recheck nameplate vs. spec

-

ifications and conditions. All single phase motors have internal
thermal protection.

Three phase motors must use starters with properly sized over-
load relays. Overload relays furnished are designed for manual
reset.

CAUTION:

UNIT LIFTING EYE

Use unit lifting eyes only to lift unit as shipped fr

om

factory. Unit must be empty and disconnected from pipes,
anchors and other restraints. Use proper rigging procedures.
Failure to follow these instructions could result in injury or
property damage.

INST

ALLATION AND DESCRIPTION

(V

ented Condensate Units)

W

ARNING: EXPLOSIBLE

Do not pr

essurize receiver. Isolate receiver during leak

test. Do not plug overflow. Do not restrict vent opening to
atmosphere. Open valves slowly. Failure to follow these
instructions could result in serious injury or death.

CAUTION:

NOT A CHEMICAL PUMP

Inject boiler feed compounds fr

om chemical feed tank

into boiler feed piping – never into condensate tank. Failure
to follow these instructions could result in injury or property
damage.

W

ARNING: HIGH VOLTAGE ELECTRICITY

Disconnect and lock out power befor

e connecting or

servicing unit. Failure to follow these instructions could
result in serious injury or death.