2−4 Installation & Operation

MN414

Moisture Protection
The submersible moisture protection system consists of the non−wicking cable cap assembly and the

dual moisture sensing probes. The cable cap assembly prevents moisture from wicking through the cable

assembly even when the cable jacket has been punctured.
Dual moisture sensing probes (Warrick type) extend into the oil chamber located between the tandem

mechanical seals. Should the outer seal fail, water will enter the oil chamber through the labyrinth slinger

paths and create a water/oil emulsion in the oil chamber. The moisture detector control applies 500 volts

to the moisture probes.
The presence of water in the oil chamber increases the conductivity sufficiently to increase current flow

through the probe circuit which illuminates a warning light and activates a relay to de−energize the motor.

The leakage detector control must be purchased separately from

Charles F. Warrick Co. Normandy Ct. Royal Oak, MI 48073 (810) 549−4900.
The leakage detector control system must be connected for the warranty and the U/L listing to be valid.

For information on the relay, see www.gemssensors.com (look for Model 2800/2810 relay).

It’s circuit diagram is shown in Figure 2-3.

Figure 2-3 Moisture Sensing Circuit

1

2

3

4

6

5

7

8

9

10

RE

Motor

W1

W2

Moisture Sensors

Test Resistor

Test

Switch

Test Lamp

AC Line

To

Alarm

500V

Sec.

leakage detector control
not provided

330k

Model 2800/2810
Charles F. Warrick Co.
(810) 549-4900

IMPORTANT:
Failure to properly connect and use this leakage
detector system voids motor warranty.

Control Cable Lead Color

Black

White

Red

Orange

Green

P1

P2

W1

W2

Ground

ORDER BY COMPONENT NUMBER −−−−− *−280O−XXX

AC SUPPLY LINE

VOLTAGE & FREQUENCY

1

115V 50/60 Hz

2

230V 50/60Hz

4

480V 50/60Hz

CONTACT CONFIGURATION

TERMINAL PAIR

3-4

5-6

7 8

A

N.O.

B

N.C.

C

N.O.

N.O.

D

N.C.

N.O.

E

N.C.

N.C.

F

N.O.

N.O.

N.O.

G

N.C.

NO.

N.O.

H

N.C.

N.C.

N.O.

J

N.C.

N.C.

N.C.

N.O.

N.C.

NORMALLY OPEN
NORMALLY CLOSED
NONE PROVIDED

NEMA TYPE ENCLOSURE

1

1

4

2, 4, 6

Line voltage are nominal values
and may range from nominal
minus 15% to nominal plus 10%.