Bell & Gossett S11865A TECHNOLOGIC 1100 SERIES PUMP CONTROLLER User Manual
Page 2

Menu
Default
Allowable
Item # System Setup Display
Value
Range
Field Value
13)
GPM Destg. Val = 0
0
0-9999
Enter GPM at which destage will be forced;
“0” disables this function.
14)
GPM Destg. Pr. Tmr. = 0
0
0-999
Enter in seconds (0-999) value of GPM
forced destage proof timer.
15)
Time Forced DeStg = 0
0
0-99
Enter in hours (0-99) time after which the lag
pump will be destaged regardless of staging
method (EOC or speed.)
“0” disables this function.
16)
DP1 Proof Time
3
0-30
Pump #1 failure proof time in seconds.
17)
DP2 Proof Time
3
0-30
Pump #2 failure proof time in seconds.
18)
Software DP Failure
0
0-999
Process variable value used to determine
software pump failure. Enter 0 (zero) for
units with differential pressure switches.
19)
DP1 Start Time
30
15-60
Time period in seconds to allow Pump 1
to start prior to detecting a pump failure.
20)
DP2 Start Time
30
15-60
Time period in seconds to allow Pump 2
to start prior to detecting a pump failure.
21)
Speed Default
50
0-100
Operating speed (%) when all zones fail.
22)
D4 Fail Mode Pumps
2
0-2
Number of pumps to run when all drives fail
0 = No pumps 1 = Lead pump
2 = Both pumps
23)
Max Pump GPM
0
0-9999
End of curve pump protection.
24)
Eoc Stg Pr. Tmr
30
0-999
Proof timer (in seconds) prior to starting
lag pump, seconds.
25)
Eoc De-Stg %
50
0-100
Percentage of maximum pump GPM at a given
speed below which destaging can occur.
26)
Eoc De-Stg Pr. Tmr
30
0-999
Proof timer (in seconds) prior to
stopping lag pump.
27)
PID Index
1
1-5
Multiplier of P, I, & D variable for slower
PID response within PID index limit.
28)
PID Index Limit
0
0-150
Deviation from setpoint
within which PID Index is active.
2