Menu

Default

Allowable

Item # System Setup Display

Value

Range

Field Value

13)

GPM Destg. Val = 0

0

0-9999

Enter GPM at which destage will be forced;

“0” disables this function.

14)

GPM Destg. Pr. Tmr. = 0

0

0-999

Enter in seconds (0-999) value of GPM

forced destage proof timer.

15)

Time Forced DeStg = 0

0

0-99

Enter in hours (0-99) time after which the lag

pump will be destaged regardless of staging

method (EOC or speed.)

“0” disables this function.

16)

DP1 Proof Time

3

0-30

Pump #1 failure proof time in seconds.

17)

DP2 Proof Time

3

0-30

Pump #2 failure proof time in seconds.

18)

Software DP Failure

0

0-999

Process variable value used to determine

software pump failure. Enter 0 (zero) for

units with differential pressure switches.

19)

DP1 Start Time

30

15-60

Time period in seconds to allow Pump 1

to start prior to detecting a pump failure.

20)

DP2 Start Time

30

15-60

Time period in seconds to allow Pump 2

to start prior to detecting a pump failure.

21)

Speed Default

50

0-100

Operating speed (%) when all zones fail.

22)

D4 Fail Mode Pumps

2

0-2

Number of pumps to run when all drives fail

0 = No pumps 1 = Lead pump

2 = Both pumps

23)

Max Pump GPM

0

0-9999

End of curve pump protection.

24)

Eoc Stg Pr. Tmr

30

0-999

Proof timer (in seconds) prior to starting

lag pump, seconds.

25)

Eoc De-Stg %

50

0-100

Percentage of maximum pump GPM at a given

speed below which destaging can occur.

26)

Eoc De-Stg Pr. Tmr

30

0-999

Proof timer (in seconds) prior to

stopping lag pump.

27)

PID Index

1

1-5

Multiplier of P, I, & D variable for slower

PID response within PID index limit.

28)

PID Index Limit

0

0-150

Deviation from setpoint

within which PID Index is active.