Fiberglass basin installation reference guide – Xylem IMCPFIBRGL R01 Fiberglass Basin User Manual

Page 6

Advertising
background image

6

30º Maximum

Lifting cable or chain

Finish grade

Optional lifting lugs

Slope and size of excavation as

pipe area and engineer’s

specification. In the absence of

these, consider continuation of

soil, depth of excavation and

safety considerations.

Basin anti-flotation flange

Compacted sub-base and/or

concrete slab as per engineer’s

specification.

Spreader bar

18” minimum backfill

compacted to a minimum

soil modules of 700 PSI

Finish grade

Fiberglass Basin as

required per

engineer’s

specification

Backfill material

Concrete grout as

required per

engineer’s

specification

NOTE: The intent of these installation instructions and illustrations is to ensure that

damage or premature failure to the basin will not occur. These installation instructions

and illustrations are NOT intended to preclude normal safety procedures which should

be followed to prevent injury to personnel. SAFE INSTALLATION PROCEDURES SHALL

BE ENTIRELY THE RESPONSIBILTY OF THE INSTALLER.

Pea Gravel

Crushed Brick

BACKFILL MATERIAL REQUIREMENTS

1”

3/4”

1/2”

1/4”

In the absence of building codes, or regulations,

maintain a minimum distance of 5 feet plus a slope

of 40” from the bottom of the compacted sub-base

to the bottom of the adjacent structure’s foundation,

footing or property line.

45”

minimum

5”–0”

minimum

Adjacent structure, foundation,

footing or property line

CAUTION:

HANDLE WITH CARE

DO NOT DROP

DO NOT IMPACT

DO NOT ROLL

DO NOT WRAP

Cable or chain

around basin

Compacted sub-base

minimum 12” or 8”

when used with concrete

hold-down pad

FIBERGLASS BASIN INSTALLATION REFERENCE GUIDE