FAULT CODES

No Light: Low Voltage or No Voltage to Controller

Green Light Codes:

• Constant Green - Unit in Standby: system is Off or system detected low

voltage, below 190 VAC and is waiting for voltage to increase to acceptable
level.

• Blinking Green - Pump is running: all is normal

Red Light Codes:

• Constant Red - Controller Error: internal controller issue, replace controller.

• 2 Blinks - Dry Well: controller will restart automatically

• 3 Blinks - Transducer Fault: controller will not run if the signal from the

transducer is disconnected or out of tolerance.

• 4 Blinks - Over Current: controller will attempt to restart three times before

displaying this fault. To clear the fault, turn power off, wait 1 minute, turn
power on. Fault may be caused by setting Overload Dial on too low a setting.

• 5 Blinks - Short Circuit: controller will attempt to restart three times, to clear,

turn power off, wait 1 minute, turn power on.

• 6 Blinks - Ground Fault: controller will not restart - To clear the fault, turn

power off, wait 1 minute, turn power on.

• 7 Blinks - Temperature: controller will restart automatically when the

temperature reaches an acceptable level.

• 8 Blinks - Open Lead: controller will not restart. To clear the fault, turn power

off, wait 1 minute, turn power on.

• 9 Blinks - Low Pressure Cut-off: Controller will not restart. Pressure 20 PSI

below set point for 30 seconds. May be a broken pipe or tripped pressure
relief valve.

Note - In many instances the controller is blamed for faults caused by bad motors, tanks
with incorrect or no air charge, poor wiring and/or improper grounding. Since the SOLO
may be used to retrofit an existing installation into a variable speed system, IM229 includes
instructions on checking Motor Insulation Resistance and Winding Resistance. Before
replacing a SOLO drive on a retrofit installation please perform these tests to verify the
motor and wire are in good condition and the tank pressure is set properly.