AO55

Frequency

Power

Sensor

4-20 mA

-

+

4-20 mA Device

(e.g. Pump, PLC,

Chart Recorder)

24-36 Vdc

Power Supply

(may be

included in

control unit)

Mechanical

Sensor

Red
White
Black

-

+

-

+

S

+

_

S

+

+

_

_

Magmeter

Terminal Block

AO55

Terminal

Block

Power

Forward

Output

24 Vdc -

+

Wiring AO55 to

Mechanical Meter

Wiring AO55 to Magmeter

Green

White

(Either/Or)

LT-65200015-B

6/24/09

Seametrics Incorporated • 19026 72nd Avenue South • Kent, Washington 98032 • USA

(P) 253.872.0284 • (F) 253.872.0285 • 1.800.975.8153 • www.seametrics.com

CONNECTIONS and TROUBLESHOOTING

TROUBLESHOOTING

CONNECTIONS

Problem

Probable Cause

Try...

No analog signal at

reading device

Output stuck at 4 mA

mA signal does not

match flow rate

Break in current loop

Dead power supply

Reversed polarity

No frequency input from flow sensor

Inadequate voltage

Wrong frequency setting

Check if loop indicator light is on

Check multimeter voltage on power supply

Check polarity

Check if flow sensor rotor is turning freely

(mechanical meters only)

Check flow sensor connections

Check flow sensor polarity

Be sure terminal blocks are firmly plugged in

With flow sensor disconnected, use short wire

to repeatedly short between sensor “sig” and

“-” terminals. Output should rise.

Verify 3-second pulse output (EX meters only)

Check load vs. supply chart

Review setting procedure

Check multimeter voltage on power supply

The AO55 can be wired to either a mechanical meter or a magmeter. See

alternative configurations below.