Oversized Pumps: Pumps should not be so large as to produce flow rates that may eventually erode

holes in the pipes. According to the Copper Development Association, excessive erosion occurs at a

velocity of about 5 ft. (1.5m) per second and higher; or about 4 GPM (15 LPM) in 1/2” (5/8”) Type M

copper pipe; and 8 GPM (30 LPM) in 3/4” pipe. Use the recommended recirculation line size shown in

the Pump Selection Guide. Laing pumps are sized so that flow velocities are well below these limits.

Pump Selection Guide: The Laing SM and UC 303/353 models are designed to handle the

recirculation requirements of residences with a pipe loop (the total length of hot water supply line

plus the recirculation line) up to 250 feet (76 M) while the SM-909/959 model pump is designed to

handle the circulation requirements of residences and small apartment complexes with pipe loop runs

to 700 or 1000 feet (213 - 304 M). The chart below provides a simple rule of thumb to help you match

the pump to your system.

UC Prefix denotes UltraCirc Housing

The 3rd digit T denotes with timer

Maximum Pressure 150 psi (10 BAR)

Maximum Temperature 230ºF (110ºC)

Installation and Start-Up

1. Select the sink under which to connect the recirculation line (the sink where the hot water takes

longest to arrive which is usually the sink farthest from the water heater).

2. Plan your installation. Decide on the course of the recirculation pipe (also determining the length

of the pipe required) and whether the return line should be connected to the water heater cold water

inlet line (tee fitting required) or to the bottom water heater drain valve (“Y” type fitting required to

fit to existing drain valve outlet). See figure 1 and 2 for the installation schematic.

Australia

This pump must be installed in accordance with AS3500.

U.L. Caution

This pump has been tested using water only. Its suitability for use with liquids other than

water is the end user’s responsibility.

Model

Volts

Cycle

Watts

Amps

SM-303-B

115

60

33

.03

SM-303-B

230

60

33

.15

SM-353-B

230

50

28

.13

SM-909-B-14

115

60

65

.58

SM-909-B-14

230

60

65

.29

SM-959-B-14

230

50

55

.25

SM-909-B-18(21, 26)

115

60

98

.95

SM-909-B-18(21, 26)

230

60

98

.47

SM-959-B-18(21, 26)

230

50

82

.40

SM-1212-B-26

115

60

140

1.22

SM-1212-B26

230

60

140

.61

SM-1252-B-26

230

50

115

.61

Housing Codes

Material/Connection

Available On

BS 1/2

Brass 1/2” (5/8”) Sweat

All

BT 1/2

Brass 1/2” (5/8”) Threaded Female NPT

303

BS 3/4

Brass 3/4” Sweat

909/1212

ST 3/4

Stainless 3/4” Threaded Female NPT

909/1212

BF

Bronze 3/4” Flanged

909/1212

HF

Cast Iron 3/4” Flanged

909/1212

Note: Sizes in parentheses are Australian pipe sizes