Warnings and alarms – Bell & Gossett P2001489 Integrated Technologic with Sensorless Control User Manual
Page 43

Number Description
Warning
Alarm/Trip
Alarm / Trip Lock
Parameter Reference
59
Current limit
X
60
External interlock
X
62
Output frequency at
maximum limit
X
64
Voltage limit
X
65
Control board over-
temperature
X
X
X
66
Heat sink temperature
low
X
67
Option configuration has
changed
X
69
Pwr. card temp
X
X
70
Illegal FC configuration
X
71
PTC 1 safe stop
X
X
1)
72
Dangerous failure
X
1)
73
Safe stop auto restart
76
Power unit setup
X
79
Illegal PS config
X
X
80
Drive initialized to
default value
X
91
Analog input 54 wrong
settings
X
92
NoFLow
X
X
22–2*
93
Dry pump
X
X
22–2*
94
End of curve
X
X
22–5*
95
Broken belt
X
X
22–6*
96
Start delayed
X
22–7*
97
Stop delayed
X
22–7*
98
Clock fault
X
0–7*
201
Fire M was active
Warnings and alarms
Warning/Alarm
Description
Cause
Remedy
1 — 10 V low
The control card voltage is
below 10 V from terminal
50.
A short in a connected
potentiometer or improper
wiring of the
potentiometer.
Remove the wiring from
terminal 50. If the warning
clears, the problem is with
the customer wiring.
Troubleshooting
Integrated Technologic
®
with Sensorless Control INSTRUCTION MANUAL
41