Bell & Gossett S13654B Technologic 5500 Series Pump Controller User Manual
Page 28

28
Analog Value, 38
Setpoint #10
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 39
Setpoint #11
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Object Identifier
Object Name
Object Type
Present Value/Range
UNIT Used
Analog Value, 40
Setpoint #12
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 41
Setpoint #13
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 42
Setpoint #14
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 43
Setpoint #15
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 44
Setpoint #16
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 45
Speed %
ANALOG_VALUE
0 to 100
Analog Value, 46
Lead Pump Number
ANALOG_VALUE
1 to Pump # (in Technologic User Setup Menu)
Analog Value, 47
Active Zone Number
ANALOG_VALUE
1 to Zone # (in Technologic User Setup Menu)
Analog Value, 48
Operation Mode
ANALOG_VALUE
0=Manual, 1=Auto, 2=Auto Bypass,
3=Manual Bypass.
Technologic 5500
BACnet Communication Objects List (continued)