Technologic

®

Constant Speed Pump Controller Installation, Operation and Maintenance Manual

38

Serial Communications Points

Description

Read

Write Range/Value

Modbus

Bacnet

Lonworks

N2

Address

Address NV Index Address

Pump2 State

X

0=Disabled, 1=Run, 2=Ready, 30002

AI 2

45

ADI 2

3=Failed

Pump3 State

X

0=Disabled, 1=Run, 2=Ready, 30003

AI 3

46

ADI 3

3=Failed

Pump4 State

X

0=Disabled, 1=Run, 2=Ready, 30004

AI 4

47

ADI 4

3=Failed

Pump5 State

X

0=Disabled, 1=Run, 2=Ready, 30005

AI 5

48

ADI 5

3=Failed

Pump6 State

X

0=Disabled, 1=Run, 2=Ready, 30006

AI 6

49

ADI 6

3=Failed

Suction/Return Pressure

X

X*

0-Span

30007/

AI 7/AO 1

50/63

ADI 7

40001

System/Supply Pressure

X

X*

0-Span

30008/

AI 8/AO 2

51/64

ADI 8

40002

Flow

X

X*

0-Span

30009/

AI 9/AO 3

52/65

ADI 9

40003

Temperature (4-20mA)

X

X*

0-Span

30010/

AI 10/AO 4

53/66

ADI 10

4004

Pressure

X

X*

0-Span

30011/

AI 11/AO 5

54/67

ADI 11

4005

Differential Temperature

X

X*

0-Span

30012/

AI 12/AO 6

55/68

ADI 12

4006

Suction/Return Temp (RTD)

X

Actual °F

30013

AI 13

56

ADI 13

System/Supply Temp (RTD)

X

Actual °F

30014

AI 14

57

ADI 14

Amps

X

Actual Amps

30015

AI 15

58

ADI 15

Horsepower

X

Actual Horsepower

30016

AI 16

59

ADI 16

* “AI Ovrd” must be set to “Y” for the corresponding sensor type in the communications setup screen in order to be writable.

See section 4.3.10.5 for more information on analog input override.