WARNING: CHLORINE & AGGRESSIVE

WATER HAZARD The water quality can

signifi cantly infl uence the life of your

product. You should test for corrosive

elements, acidity, total solids, and other relevant

contaminants, including chlorine and treat your water

appropriately to insure satisfactory performance and

prevent premature failure. Failure to follow this

instruction may result in serious personal injury or

death and property damage.

SYSTEM VENTING AND PURGING

After initial venting and purging of air from the system,

more air will be released from the water as it is heated.

Therefore, it is recommended that a Bell & Gossett air

separator be installed on the main.

If the system has multiple loops or zones, the supply

water for all loops and zones must pass through the air

separator for complete and continuous air removal. In

case the piping arrangement does not permit the

installation of a single air separator on the main, air

separators should be installed on each loop or zone. In

this event, only one expansion tank is required for the

system.

Even with a Bell & Gossett air separator installed on the

main or mains, it is recommended that Bell & Gossett air

vents be installed on high points in the system.

It is also recommended that manual (key or coin type) air

vents be installed at higher points on the radiation.

OPERATING INSTRUCTIONS

1. The expansion tank is typically installed in the bottom

of an air separator. Its sealed-in air pre-charge prevents

water from entering the tank until the system pressure

exceeds the pre-charge pressure

2. As the water temperature rises, expanded water enters

the expansion tank’s water reservoir. The pre-charge air

chamber absorbs the pressure increase, keeping system

pressures below the relief valve setting.

3. As water temperature decreases the pressure in the

air chamber forces water back into the system until the

expansion tank is empty.

The selection, application, installation and servicing of

this product should be performed by a qualifi ed

professional within all applicable safety and code

requirements.

Air

Cushion

Air

Cushion

Air

Cushion

Air

Cushion

Air

Cushion

Air

Cushion

Models PT-5

and PT-12

Models PT-25V

and PT-475

WARNING: RUPTURE OR EXPLOSION

HAZARD Like most pressurized tanks, this

tank can over time corrode, weaken, and

burst or explode. Failure to follow this

instruction may result in serious personal injury or death

and property damage.

Back Flow Preventer Check Valve

PT Tank

Hot Water

CWS

Relief Valve

Typical Instillation

Figure 1

Water

Heater