2. For installing NPT connections:

Apply pipe compound conservatively to male connecting

fittings only.

After installation check all joints for leakage and retighten

where necessary.

OPERATION INSTRUCTIONS

1. Energize the zone, circuit and/or system pump(s) as

applicable.

2. Using Bell & Gossett Model RP-250B Readout Probes,

sequentially attach a Bell & Gossett differential pressure

readout kit to the readout valves on each Venturi/Ball

valve.

3. Read the differential pressure across the orifice of the

Venturi/Ball valve.

4. Using the differential pressure data sheet #EP-600 of the

Venturi/Ball valve to read actual GPM.
Example: The Venturi/Ball valve model 3/4" L. If the dif-

ferential pressure across the orifice read at 46" W.C. the

flow rate is 4 GPM.

HOW TO USE THE MEMORY STOP FEATURE
1. Make the final degree of closure setting.

2. Loosen the handle nut and rotate memory stop until

against the body locking.

3. Tighten the handle nut.

SERVICE INSTRUCTIONS

Periodically inspect the Venturi/Ball for signs of leakage or

corrosion.

WARNING: Use of improper procedures to sweat

valve model with union connection into system can

damage valve. Before installing sweat union connection to

valve, remove the union nut and O-ring from the valve

body, then union tailpiece with union nut must be sweated

(soldered) into place. Failure to follow this instruction could

result in property damage and/or moderate personal injury.

CAUTION: Heat Associated with the use of silver

solder may damage a Venturi/Ball valve and void the

product warranty. Do not use silver solder. Failure to follow

these instructions could result in property damage and/or

moderate personal injury

CAUTION: The use of PTFE impregnated pipe

compound and PTFE tape on pipe threads provides

lubricity. Care should be taken to prevent overtightening

which may damage the valve body. Failure to follow these

instructions can result in moderate personal injury and/or

property damage.

WARNING: Hot water leakage can occur from read-

out valves during probe insertion and during hookup

of readout kit. Follow the instruction manuals supplied with

readout probes and readout kits for safe use. Failure to

follow these instructions could result in serious personal

injury or death and property damage.

WARNING: Corrosion or leakage is indication, that

the Venturi/Ball must be replaced. Failure to follow

these instructions could result in serious personal injury or

death and property damage.

Xylem Inc.

8200 N. Austin Avenue

Morton Grove, Illinois 60053

Phone: (847) 966-3700

Fax: (847) 965-8379

www.xyleminc.com/brands/bellgossett

Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. V57895B September 2012