Operation – Xylem MM 221G Models 157S RBP MD Low Water Cut-Offs/Pump Controllers User Manual

Page 2

Advertising
background image

Pump or Motorized Valve

Circuit Rating (Amperes)

Voltage

Full Load

Locked Rotor

Pilot Duty

120 VAC

7.4

44.4

345 VA at

240 VAC

3.7

22.2

120 or 240 VAC

Approximate

Distance Above

Cast Line

Differential

Setting

In. (mm)

In. (mm)

Pump Off

5

1

/

2

(140)

1

1

/

2

(38)

Pump On

4

(102)

Pump Off

15

/

16

(24)

3

/

8

(16)

Pump On

9

/

16

(14)

Burner Off

0

N/A

Pump Off

1

7

/

16

(37)

3

/

4

(19)

Pump On

11

/

16

(17)

Burner Off

-

3

/

8

(-16)

N/A

2

PUMP OFF

CAST LINE

3

/

8

"

(35mm)

9

/

16

"

(16mm)

PUMP ON

BURNER OFF

CASTING LINE

PUMP ON

PUMP OFF

;

;

;

;

;;

;;

;;

1

1

/

2

"

(38mm)

4"

(102mm)

OPERATION

Maximum Pressure: 150 psi (10.5 kg/cm

2

)

Electrical Ratings
Float Control

Probe Control (750BM-P-120-CI)

157S-RBP-MD

Settings and Differential Pressures:

Probe Sensitivity:
- 26,000 ohms

Probe Input Power
- 120 volts

Pump or Motorized Valve

Circuit Rating (Amperes)

Voltage

Full Load

Locked Rotor

120 VAC

7.2

43.2

240 VAC

3.75

21.6

Probes Any

Pressure

Float

0 psi

(0 kg/cm

2

)

Float

150 psi

(10.5 kg/cm

2

)

Pressure

Alarm Circuit Rating

Voltage

Amps

120 VAC

1

240 VAC

1/2

Motor Horsepower

Voltage

Amps

120 VAC

1/3

240 VAC

1/3

* Values are ±

8" (3.2mm).

Probe Settings

Float Settings (0 psi)

Advertising