24V Burner/120V Feeder

120V Burner/120V Feeder

or

24V Burner/24V Feeder

Connect a wire from the "Hot" side of the power supply to the
water feeder terminal 3, and low water cut-off terminal 2.
Connect a wire from the neutral side of the power supply to the
water feeder terminal 2, and to the neutral side of the burner.

Connect the wire from the burner to terminal 1 of the low water
cut-off. Connect a jumper from terminal 2 to terminal 3 of the
low water cut-off. Connect a wire from terminal 4 of the low
water cut-off to terminal 1 of the water feeder.

W
or

1

N

or

2

H

or

3

BURNER

1

2

3

4

N

H

WF2-U-120 or
WF2-U-24

Supply Voltage

SAME as Feeder

69

120V Burner/24V Feeder

W
or

1

N

or

2

H

or

3

BURNER

24V
TRANSFORMER

1

2

3

4

N

120 VAC

SUPPLY

H

WF2-U-24V

69

Switch

Initial

Initial

Dwell/Feed

Position

Dwell

Feed

Cycles

M&M

60

60

Repeats until LWCO

seconds

seconds

reactivates the

burner circuit

2

90

90

One

seconds

seconds

3

100

100

One

seconds

seconds

2

3

M

&M

M&M

2

3

Wiring Diagrams (continued):
Series 69 Low Water Cut-off with M&M Model WF-2-U Electronic Water Feeders

The Uni-Match

®

water feeders have a three-position slide

switch which initiates a dwell period specific to the position of
the switch. If the system condensate raises the boiler water
level above the cut-off level during the dwell period, no addi-
tional water will be added to the boiler. Once the dwell period
has passed, the feeder will be activated and water will be
added to the boiler. The feeder will be deactivated when the
LWCO reactivates the burner circuit.

The position of the slide switch also sets the length of the
dwell period, the length of time valve is open and the number
of dwell/feed cycles. The control is set with the slide switch in
position 3 and can be changed in the field after installation.
The chart on the right indicates the cycles and length of
dwell/feed cycles for each position.

6

W
or

1

N

or

2

H

or

3

BURNER

24V

TRANSFORMER

1

2

3

4

N

120 VAC
SUPPLY

H

WF2-U-120

69

WIRING ALTERNATIVES

WHEN USING MIXED VOLTAGES