Dual pump control, Motorized valve and low water cut-off – Xylem MM 286B Series 1575 – Low Water Cut-Off/Pump Controller User Manual

Page 7

Advertising
background image

7

• Connect wire “ a ” from power supply to

t e rminal “ H ” .

• Connect wire “ b ” from neutral supply to

t e rminal “ N ” .

• Connect wire “ c ” from pump control circuit

to terminal “ P N O ” .

• Connect wire “ d ” from pump control circuit

to terminal “ P C O M ” .

• Connect wire “ e ” from bu rner control

circuit to terminal “ B N O ” .

• Connect wire “ f” from alarm control circuit

to terminal “ B N C ” .

• Connect wire “ g ” from bu rner or alarm

control circuit to terminal “ B C O M ” .

WIRING DIAGRAMS
Low Water Cut-Off, Alarm and Pump Up Control

• Connect wire “ a ” from power supply to

t e rminal “ H ” .

• Connect wire “ b ” from neutral supply to

t e rminal “ N ” .

• Connect wire “ c ” from pump #1 control

circuit to terminal “ P N O ” .

• Connect wire “ d ” from pump #1 control

circuit to terminal “ P C O M ” .

• Connect wire “ e ” from pump #2 control

circuit to terminal “ B N C ” .

• Connect wire “ f” from pump #2 control

circuit to terminal “ B C O M ” .

Dual Pump Control

• Connect wire “ a ” from power supply to

t e rminal “ H ” .

• Connect wire “ b ” from neutral supply to

t e rminal “ N ” .

• Connect wire “ c ” from va l ve control circuit

to terminal “ P N O ” .

• Connect wire “ d ” from va l ve control circuit

to terminal “ P C O M ” .

• Connect wire “ e ” from bu rner control

circuit to terminal “ B N O ” .

• Connect wire “ f” from alarm control circuit

to terminal “ B N C ” .

• Connect wire “ g ” from bu rner or alarm

control circuit to terminal “ B C O M ” .

Motorized Valve and Low Water Cut-Off

FROM BURNER OR ALARM

CONTROL CIRCUIT

TO ALARM

CONTROL CIRCUIT

TO BURNER

CONTROL CIRCUIT

FROM PUMP UP

CONTROL CIRCUIT

TO PUMP UP

CONTROL CIRCUIT

NEUTRAL

HOT

BCOM

BNC

BNO

PCOM

PNC

PNO

N

H

g

f

e

d

c

b

a

FROM PUMP #1

CONTROL CIRCUIT

FROM PUMP #2

CONTROL CIRCUIT

TO PUMP #2

CONTROL CIRCUIT

TO PUMP #1

CONTROL CIRCUIT

NEUTRAL

HOT

BCOM

BNC

BNO

PCOM

PNC

PNO

N

H

f

e

d

c

b

a

FROM VALVE

CONTROL CIRCUIT

TO VALVE

CONTROL CIRCUIT

NEUTRAL

HOT

BCOM

BNC

BNO

PCOM

PNC

PNO

N

H

d

c

b

a

FROM BURNER OR ALARM

CONTROL CIRCUIT

TO ALARM

CONTROL CIRCUIT

TO BURNER

CONTROL CIRCUIT

g

f

e

Advertising