OPERATION

Capacities

WATER SUPPLY PRESSURE IN LBS. PER SQ. IN.

CAPACITY CURVE

lbs./hr.

psi

(kg/hr.)

130

120

110

100

90

80

70

60

50

40

30

10

16,000
15,000
14,000
13,000
12,000
11,000
10,000

9,000
8,000
7,000
6,000
5,000
4,000
3,000
2,000

1,000

0

(7258)
(6804)
(6350)
(5897)
(5443)
(4990)
(4536)
(4082)
(3629)
(3175)
(2722)
(2268)
(1814)
(1361)

(907)
(454)

(0)

(0.7)(1.4)(2.1)(2.8)(3.5)(4.2)(4.9)(5.6)(6.3)(7.0)(7.7)(8.4)(9.1)(9.8)(10.5)

20

0

(0)

140 150

32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0

(121.12)
(113.55)
(105.98)
(98.41)
(90.84)
(83.27)
(75.70)
(68.13)
(60.56)
(52.99)
(45.42)
(37.85)
(30.28)
(22.71)
(15.14)
(7.57)
(0)

(kg/cm

2

)

gpm

(lpm)

464
435
406
377
348
319
290
261
232
203
174
145
116
87
58
29
0

(4549)
(4264)
(3980)
(3696)
(3411)
(3127)
(2843)
(2559)
(2274)
(1990)
(1706)
(1421)
(1137)
(853)
(569)
(284)
(0)

Boiler Hp

(kilowatts)

The Series 21 make-up water feeder provides
dependable, float-operated automatic water filling
service to tanks used as condensate receivers in
boiler systems. The valve components are of brass,
an elastomer sealing disc and stainless steel materi-
als, and a 4-3/4” diameter copper float providing

closure against supply pressure up to 150 PSI. An
integral strainer and housing with removable drainage
plug precede the valve for regular servicing. The con-
trol is a direct-feeding unit (feeds through the flange
connection) available in two flange sizes.

TYPICAL INSTALLATIONS

MODEL 221

Boiler

Feed

Tank

Feed Pump

City Water Supply

Check Valve

Bypass

Condensate Receiver Tank

Pump

Discharge

Feed Pump

MODEL 21

Advertising