Maintenance, Step 4 - switch adjustment – Xylem MM 704B No. 2 Switch For series 47, 247, 63, 51, and 53 water feeders to add the low water cut-off function User Manual

Page 4

Advertising
background image

Xylem Inc.

8200 N. Austin Avenue

Morton Grove, Illinois 60053

Phone: (847) 966-3700

Fax: (847) 965-8379

www.xyleminc.com/brands/mcdonnellmiller

McDonnell & Miller is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. MM-704B April 2012 Part No. 210529

MAINTENANCE:

• Replace the switch every 10 years or when the components do not operate properly. More frequent

replacement may be required when severe conditions exists.

The control and switch have been factory adjusted and should not need any further adjustment in the field.
Observe the devices being activated by the control and switch and, should adjustment be needed, follow
the following steps.

STEP 4 - Switch Adjustment

L

M

a. Using a flat head screwdriver and 5/16” nut

driver, loosen adjusting screw (M) until cam
is set in lowest position.

b. Slowly, turn adjusting screw (M) raising the

cam until the switch clicks, opening the
common and normally closed contacts. Hold
adjusting screw (M) in position and tighten
nut (L) using 5/16” nut driver on the opposite
end.

c. Observe the devices being activated by the switch

and control to determine if the switch is activating
when desired.
If further adjustment is required, repeat Step c.

3

Neutral

120 V.A.C.

Supply Hot

Used as a Mainline Switch�

and/or Low Water Alarm

FIGURE 1

Used as a Pilot Switch to Coil�

of Relay or Motor Starter

Low

Water
Alarm

Load

Load

Line

C.

N.C.

N. O.

C.

N.C.

N. O.

b. Using copper wire only, follow the wiring

diagrams in Figure 1 to wire the No. 2
Switch. Terminals C and NC are the low
water cut-off switch. Terminals C and NO
are the alarm switch. If the electrical load
exceeds the rating of the switch, use an
auxiliary relay or motor starter.

E

c. Slide the switch housing (E) onto the

switch and, using a flathead screwdriver,
tighten the two (2) screws that secure the
switch housing.

a. Check to see that the burner turns on and

off, by raising and lowering the water level
in the boiler.

b. Make sure there is travel in the float arm

after the burner goes on and off.

c. Repeat test several times.

E

a. Using the flathead screwdriver, remove the

two (2) screws that secure the switch housing (E).

STEP 2 - Electrical Wiring

STEP 3 - Testing

INSTALLATION COMPLETE

Advertising