MAINTENANCE
SCHEDULE:

• Blow down weekly during heating season.
• Check all wiring for brittle or worn insulation.

Replace control every 10 years.

TROUBLESHOOTING

Problem:
1. Control does not turn burner off on low water.
2. Control does not turn electric feeder off.

Cause:

Contacts may be fused from overload.

Test:

With a continuity meter or ohm meter check if both

circuits open as the rocker is moved through its operating

range.

Solution:

Replace the switch if either circuit remains closed

through the test. Refer to the installation / replacement

procedure.

If the switch functions normally off of the control, inspect the float and

interior chamber condition for obstructions and debris, especially

around the bellows area and at the gauge glass end.

Follow ASME Boiler and Pressure
Vessel Code - Section VI Paragraph
7.07G.

It states that the controls

should be dismantled annually by

qualified personnel, to the extent

necessary to insure freedom from

obstructions and proper functioning of

the working parts.