Step 2 - testing, Proceed to step 2 to test control, Caution – Xylem MM 706B Replacement Switch Assembly User Manual

Page 2

Advertising
background image

2

3

OFF

ON

STEP 1 - Removal and Replacement of Contacts and Terminal Panels

a. Turn power off to boiler and all controls.

Allow boiler to cool to 80˚F (27˚C) and
reduce the pressure to 0 psi (0 bar).

TOWER TUBE

SWITCH
ASSEMBLY

TERMINAL
CONNECTIONS

SWITCH
COVER

TERMINAL
PANELS

CONDUIT
CONNECTOR

NAMEPLATE

FITTING
HUB

C

A

b. Remove and Replace Switch Assembly

• Remove two screws (A) and lift off

switch cover.

• Identify terminal connections for

rewiring and then disconnect all wires
from terminal panels.

• Remove conduit connector and wires

from the integral fitting hub.

• Remove four hex nuts (B) and carefully

lift switch assembly up and off
tower tube.

• Carefully slide new switch assembly

over tower tube and secure with four
hex nuts (B). Make sure nameplate is
in same position as old unit.

• Remove two screws (A) and lift switch

cover off new unit.

• Install conduit fitting from old unit

with attached wires on switch assembly.

• Reconnect wiring to terminal panel in

exactly the same position as removed.

• Replace switch cover and fasten with

two screws (A).

STEP 2 - Testing

a. Turn on power to boiler and pump circuits.

With the boiler empty, the pump should turn on (5 or 5-M switch models) or the valve open
(7B or 7B-M switch models). The burner should remain off and boiler should begin to fill with water.

b. For Automatic Reset Models

When water level in the gauge glass is approximately 1 3/8” (35mm) above the horizontal cast line,
the burner should turn on.

For Manual Reset Models
When water level in the gauge glass is approximately 1 3/8” (35mm) above the horizontal cast line,
press the manual reset button and the burner should turn on.

c. For 5 or 5-M Switch Models

When water level in the gauge glass is approximately 2 1/8” (54mm) above the horizontal cast line,
the pump should turn off.

For 7B or 7B-M Switch Models
When water level in the gauge glass is approximately 2 11/16” (68mm) above the horizontal cast
line, the valve should be closed.

d. With the water in the boiler at its normal level and burner on, SLOWLY open the blow-down valve

until it is fully open. As the water level in the gauge glass begins to drop, verify that the following
occurs.
For 5 or 5-M Switch Models
When water level drops to approximately 1 1/8” (29mm) above the horizontal cast line, the pump
should turn on.
When water level drops to the horizontal cast line, the burner should turn off.

For 7B or 7B-M Switch Models
As the water level drops, the valve should begin to open.
When the water level drops to approximately 7/8” (22mm) above the horizontal cast line, the valve
should be full open.
When the water level drops to the horizontal cast line, the burner should turn off.

e. Close the blow-down valve after burner turns off and restore water level to normal operating level.

f. Repeat testing procedure several times to ensure proper operation of control.

g. After testing and verification of control operation, the boiler can be returned to service.

– Dimensions shown are typical.
– The following testing procedure is only meant to serve as a verification of proper

operating sequence.

Proceed to Step 2 to Test Control

CAUTION

Immediately turn off all power if the burner turns on with no water in the gauge glass.
Investigate further before continuing procedure.

!

CAUTION

If pump does not turn off or valve close, turn off water supply to boiler. Investigate
further before continuing procedure.

!

There may be more than one source of power to
the boiler.

!

CAUTION

05592:MM-706

2/4/10

9:42 AM

Page 3

Advertising