Warning, Temperature and pressure relief valve, Closed system/thermal expansion – John Wood SpaceSaver (2.5 Gallon) User Manual
Page 7: Filling the water heater
 
7
5. Install a shut off valve in the cold water inlet line. It
should be located close to the water heater and be 
easily accessible. The owner/operator must be shown 
the location of this valve and be given instructions on 
how to use it to shut off the water to the heater.
6. Install a temperature and pressure relief valve and
discharge line in the opening marked “T & P RELIEF 
VALVE”. Install as specified under “Temperature and 
Pressure Relief Valve.”
7. After piping has been properly connected to the water
heater, follow the instructions in the “Filling the Water 
Heater” section of this manual.
Temperature and Pressure 
Relief Valve
For protection against excessive pressures and 
temperatures, a temperature and pressure relief valve must 
be installed in the opening marked “T & P RELIEF VALVE” 
(see Figure 5).
CAUTION: To reduce the risk of excessive pressures and 
temperatures in this water heater, install temperature and 
pressure relief protective equipment required by local 
codes, but no less than a combination temperature and 
pressure relief valve certifi ed by a nationally recognized 
testing laboratory that maintains periodic inspection of the 
production of listed equipment or materials, as meeting 
the requirements for “Relief Valves and Automatic Gas 
Shut-Off Devices for Hot Water Supply Systems”, ANSI 
Z21.22 - latest edition. This valve must be marked with the 
maximum set pressure not to exceed the marked maximum 
working pressure of the water heater. Install the valve into 
an opening provided and marked for this purpose in the 
water heater, and orient it or provide tubing so that any 
discharge from the valve exits only within 300mm (12 in.) 
(Can.), 6 in. (150mm) (U.S.A.), above, or at any distance 
below, the structural fl oor, and does not contact any live 
electrical part. The discharge opening must not be blocked 
or reduced in size under any circumstance.
IMPORTANT: Only a new temperature and pressure relief 
valve should be used with your water heater. Do not use an 
old or existing valve as it may be damaged or not adequate 
for the working pressure of the new water heater. Do not 
place any valve between the relief valve and the tank.
The Temperature & Pressure Relief Valve:
• 
Shall not be in contact with any electrical part.
•
Shall be connected to an adequate discharge line.
•
Shall not be rated higher than the working pressure 
shown on the rating plate of the water heater.
The Discharge Line:
• 
Shall not be smaller than the pipe size of the relief 
valve or have any reducing coupling installed in the 
discharge line.
•
Shall not be capped, blocked, plugged or contain 
any valve between the relief valve and the end of the 
discharge line.
•
Shall terminate a maximum of 300mm (12 in.) (Can.), 6 
in. (150mm) (U.S.A.), above a floor drain or external to 
the building.
•
Shall be of material listed for hot water distribution.
•
Shall be installed to allow complete drainage of both 
the valve and discharge line.
Closed System/Thermal Expansion
Periodic discharge of the temperature and pressure relief 
valve may be due to thermal expansion in a closed water 
supply system. The water utility supply meter may contain a 
check valve, backflow preventer or water pressure reducing 
valve. This will create a closed water system. During 
the heating cycle of the water heater, the water expands 
causing pressure inside the water heater to increase. This 
may cause the temperature and pressure relief valve to 
discharge small quantities of hot water. To prevent this, it 
is recommended that a diaphragm-type expansion tank 
(suitable for potable water) be installed on the cold water 
supply line. The expansion tank must have a minimum 
capacity of 5.6 litres (1.5 U.S. gallons) for every 190 litres 
(50 U.S. gallons) of stored water. Contact the local water 
supplier or plumbing inspector for information on other 
methods to control this situation.
IMPORTANT: Do not plug or remove the temperature and 
pressure relief valve.
Filling the Water Heater
Do not insert the power cord into the electrical receptacle 
until all the following steps have been completed.
1. Open all hot water faucets served by the system to al-
low air to escape from the tank.
2. Open the cold water inlet valve.
NOTE: When filling, avoid water leakage. Do not allow 
the insulation of the water heater to get wet as water can 
reduce the effectiveness of the insulation.
Failure to follow these instructions can
result in death or explosion.
Do not remove valve.
Do not plug valve.
Examples of a qualified person include:
licensed plumbers, authorized gas company
personnel, and authorized service
personnel.
If the temperature and pressure relief valve
is dripping or leaking, have a qualified
person replace it.
Explosion Hazard
WARNING