IV. Manual Override

The EMBC has a manual override that allows the user to
manually open and close the bleed valve. Use the manual
override to identify the minimum flow set point to avoid
surge and the minimum flow set point necessary to close
the valve without causing "hunting" of the valve. To enter
the manual mode, press both the Up button (10) and the
Down button (7) simultaneously. Both the Amps LED (3)
and the SCFM LED (4) will flash. The digital display (11)

V. Wiring Diagram

Specifications

Dimensions (H x W x D)

Overall 5

1

/

8

x 6

1

/

8

x 3

Cutout 4

3

/

4

x 5

3

/

4

x (n/a)

Part Number CTB 90008

Digital Display

7 Segment / LED

5

/

8

High

Display Amps / SCFM

Power Supply

120/240 VAC, 1Ø, 50/60 Hz

Inputs

Analog (1)

0-5A Current Transformer

Digital (2)

120 VAC (Enable, Reset)

Outputs

(2) Provided Rated @: 5 A General

Valve Open

Purpose, 250 VAC;

1

/

6

HP 120 VAC,

Valve Close

2A Pilot Duty, 120 VAC

Nema Ratings

1, 12, 4, 4X

Note: N-12, 4 and 4X, Indoor Only

Agency Approvals

UL 873

File #E151368, 97ME50259, DD/215K

CUL

CAN/CSA 22.2, No. 24-93

will show motor amps only. Now press the Up button (10) to
manually open the valve or the Down button (7) to manually
close the valve. The corresponding valve LED will illuminate.
To exit the manual mode, press the Reset/Enter "R/E" button
(8). The last display mode will then appear (Amps or SCFM).
Note: If no operator control is initiated for 30 seconds,
the control will revert to automatic.