OM−05521

SUPER T SERIES

OPERATION

PAGE C − 4

As long a the Low Temperature Thermostat
contacts are closed, the display will show lo

tpt" unless

switch is pressed to display

some other information. Level is not viewable
until the Low Temperature Thermostat con-
tacts open.

The user may wish to check Setpoints Off/On

delay times. Bumping" the

switch will dis-

play all of the information desired.

NOTE

One second delays in contact opening/closing is a
result of time sampling of the pressure signal to fil-
ter false signals that could cause nuisance" trip-
ping of the contacts.

NOTE

If the Hrn dLy" is pre-set from the factory through
the engine control panel, therefore this function is
not utilized through the EPS.

Use caution to ensure that the --.on" set-
point (i.e. A.on") is not adjusted to a level
less than the corresponding --.of" set-
point (i.e. A.of"). Improper adjustment of
the off/on setpoints will render the unit non-
functional, resulting in flooding.

EPS Calibration

NOTE

Zero offset and span adjustments are only neces-
sary to calibrate a new unit, or when replacing the
transducer. Once calibrated, ON" and OFF" set-
points will be stored in the unit’s memory. Liquid
level adjustments will be used whenever ON" and

OFF" liquid levels must be reset.

There are two reasons for the user to calibrate the
unit. When power is applied, the unit confirms set-
points and other calibration information for validity.
If the setpoints are not valid, the LCD screen shows

EEP bAd" and the unit must be recalibrated. Also,

if the unit is moved, or some other external change
takes place, the unit must be recalibrated.

Zero Adjustment

Zero adjustment tells the unit when the transducer
is exposed to zero water (atmospheric) pressure.
When recalibration is desired, hold the transducer
in hand and apply power to the unit. The LCD

screen will display Level ABC". Press and hold
for 5 seconds. The LCD screen displays Input?
External XDUCR". Perform the following calibration
procedures.

Press

3 times and the LCD screen will display

Calibrate Zro". Press

or

until a character or

number on the display changes.

Press

to accept the entry and advance to Cali-

brate Span".

Span Adjustment

Span adjustment calibrates the unit to a known wa-
ter pressure (depth). To set:

Submerge the transducer to an exact known
depth. At Calibrate Span", the span setting in the

unit’s memory will display. Press

to increase or

to decrease the value unitl the LCD screen dis-

play equals the actual known depth of the trans-
ducer.

Level Adjustment

Level adjustment tells the unit when to turn the
pump on and off. To set:

From Level ABC" display, press

once and

Pump Setpt A On" will display. Press

to in-

crease or

to decrease to the desired level at

which the pump turns on. Press

to advance to

Pump Setpt A Off". Press

to increase or

to

decrease to the desired level at which the pump
turns off.

Press

again to advance to Pump Setpt B On". If

B" is to be used, repeat the procedure described

above for adjusting level A".