Gorman-Rupp Pumps 11 1/2A52-E2 3P 1235018 and up User Manual

Page 13

Advertising
background image

OM-04829

10 SERIES

PAGE B - 6

INSTALLATION

DISCHARGE PIPE

DISCHARGE

CHECK VALVE

PUMP DISCHARGE

SELF‐PRIMING

CENTRIFUGAL

PUMP

SUCTION

LINE

SUPPORT

BRACKET

CLEAN‐OUT

COVER

INSTALL AIR RELEASE VALVE

IN HORIZONTAL POSITION

90

_ LONG

RADIUS

ELBOW

WET WELL

OR SUMP

BLEED LINE 1”
(25,4 MM) DIA. MIN.
(CUSTOMER FUR­
NISHED) DO NOT EX­
TEND BELOW PUMP
OFF LIQUID LEVEL

Figure 3. Typical Automatic Air Release Valve Installation

Connect the valve outlet to a bleed line which
slopes back to the wet well or sump. The bleed line
must be the same size as the outlet opening or
larger, depending on which Air Release Valve is be­
ing used. If piping is used for the bleed line, avoid
the use of elbows whenever possible.

NOTE

For multiple pump installations, it is recommended

that each Air Release Valve be fitted with an inde­
pendent bleeder line directed back to the wet well.
If multiple Air Release Valves are installed in a sys­
tem, do not direct bleeder lines to a common mani­
fold pipe. Contact your Gorman‐Rupp distributor or
the Gorman‐Rupp Company for information about
installation of an Automatic Air Release Valve for
your specific application.

Advertising
This manual is related to the following products: