Operation - section c – Gorman-Rupp Pumps T10A61S-B /FM User Manual

Page 16

Advertising
background image

SUPER T SERIES

OM-05444

OPERATION

PAGE C - 1

OPERATION - SECTION C

Review all SAFETY information in Section A.

Follow the instructions on all tags, labels and de­
cals attached to the pump.

This pump is designed to handle sew­
age, wastewater, trash and slurries con­
taining large entrained solids. Do not at­
tempt to pump volatile, corrosive, or
flammable materials which may dam­
age the pump or endanger personnel as
a result of pump failure.

Pump speed and operating condition
points must be within the continuous per­
formance range shown on the curve.
(See Section E, Page 1.)

PRIMING

Install the pump and piping as described in IN­
STALLATION
. Make sure that the piping connec­
tions are tight, and that the pump is securely
mounted. Check that the pump is properly lubri­
cated (see LUBRICATION in MAINTENANCE
AND REPAIR
).

This pump is self‐priming, but the pump should
never be operated unless there is liquid in the
pump casing.

Never operate this pump unless there is
liquid in the pump casing. The pump will
not prime when dry. Extended operation of
a dry pump will destroy the seal assembly.

Add liquid to the pump casing when:

1. The pump is being put into service for the

first time.

2. The pump has not been used for a consider­

able length of time.

3. The liquid in the pump casing has evapo­

rated.

Once the pump casing has been filled, the pump
will prime and reprime as necessary.

After filling the pump casing, reinstall
and tighten the fill plug. Do not attempt
to operate the pump unless all connect­
ing piping is securely installed. Other­
wise, liquid in the pump forced out
under pressure could cause injury to
personnel.

To fill the pump, remove the pump casing fill cover
or fill plug in the top of the casing, and add clean
liquid until the casing is filled. Replace the fill cover
or fill plug before operating the pump.

STARTING

Consult the operations manual furnished with the
power source.

OPERATION

Lines With a Bypass

If a Gorman‐Rupp Automatic Air Release Valve has
been installed, the valve will automatically open to
allow the pump to prime, and automatically close
after priming is complete (see INSTALLATION for
Air Release Valve operation).

If the bypass line is open, air from the suction line
will be discharged through the bypass line back to
the wet well during the priming cycle. Liquid will
then continue to circulate through the bypass line
while the pump is in operation.

Lines Without a Bypass

Open all valves in the discharge line and start the
power source. Priming is indicated by a positive

Advertising