Gorman-Rupp Pumps S4C65-E10 460/3 861279 thru 1142084 User Manual

Page 32

Advertising
background image

OM--04136

CONTROL BOXES

PAGE B -- 26

INSTALLATION

Table 3. 27515--571 And 27515--572 Control Box Data

CONTROL BOX DATA

CONTROL P/N

G-R P/N

27515-

C.H.

PART NO.

LIQ. LEVEL

CONTROL

RELAY

SETTING

PUMP DATA**

V

HP

Hz FLA

460 275

60

320 571

84--29709--3

5

600

EMA72

A+7/8

C+1/2

3200

STANDARD

575

C.H. P/N

A999AY523

NEMA

SIZE

CONT.

CURRENT

RATING

CONTROL

INTERFACE

MODULE

**

CONSULT INDIVIDUAL PUMP NAME PLATE FOR SPECIFICATIONS.

CIRCUIT

BREAKER

LOCKING PIN

SETTING

DIAL & TRIP

SETTING

275

60

256 572

84--29709--4

5

400

EMA72

A+1/3

C+1/2

2625

STANDARD

Table 4. Control Box Torque Values

Terminal

Torque

In. lbs. (m. kg.)

NEMA

SIZE

3

HEATER PACK

MOUNTING SCREW

RECOMMENDED TORQUE

In. lbs. (m. kg.)

24 --- 30 (0,28 --- 0,35)

4

24 --- 30 (0,28 --- 0,35)

5

9 (0,10)

1 & 2

9 (0,10)

POWER TERMINATIONS

LINE SIDE

LOAD SIDE

Wire Size

(AWG)

Wire Size

(AWG)

Terminal

Torque

In. lbs. (m. kg.)

14 --- 10

8

35 (0,40)
40 (0,46)

14 --- 10

8

35 (0,40)
40 (0,46)

Use 60/75_C Al or

Cu Conductors

Use 75_C Al or

Cu Conductors

14 --- 10

8

35 (0,40)
40 (0,46)

6 --- 4

45 (0,52)

3 --- 1/0

50 (0,58)

Use 75_C Cu

Conductors Only

14 --- 10

8

35 (0,40)
40 (0,46)

6 --- 4

45 (0,52)

3 --- 1/0

50 (0,58)

Socket Size

In. (mm)
3/16 (4,76)

1/4 (6,35)

5/16 (7,94)

3/8 (9,53)

120 (1,38)
200 (2,30)
250 (2,88)

550 (6,34)

14 --- 10

8

35 (0,40)
40 (0,46)

6 --- 4

45 (0,52)

3 --- 1/0

50 (0,58)

Use 75_C Cu

Conductors Only

550 (6,34)

Use 75_C Copper or Alumi-

num Conductors only.

Torque terminals to values

given on HMCP nameplate.

Use 75_C Al or

Cu Conductors

Use 60/75_C Al or

Cu Conductors

Use 75_C Copper or Alumi-

num Conductors only.

6 --- 4

45 (0,52)

6 --- 4

45 (0,52)

3 --- 2

50 (0,58)