9 soft start, 10 start delay, 11 current limit/short circuit protection – Alpha Technologies Cordex 48-1.2kW User Manual

Page 15: 12 power limiting, 13 high voltage shutdown (hvsd), 14 battery eliminator operation, 2 distribution module, Distribution module

Advertising
background image

030-834-J0 Rev A

Page

9 of 34

2.1.9

Soft Start

To eliminate an instantaneous demand on the AC source, a soft start feature is employed. Soft Start,

sometimes referred to as “current walk-in”, works by gradually (up to five seconds) ramping the current limit

up from zero to the actual or defined customer setting. The rectifier output voltage is ramped up from the

minimum voltage to the float voltage.

2.1.10

Start Delay

The rectifier modules are equipped with a delay timer in order to stagger start a series of modules to

prevent excessive loading of generators upon start up. The built-in timer delays the turn on of the module

depending on the value selected (up to 120 seconds) via the CXC. A minimum one-second delay is preset

to allow charging of the input capacitors.

2.1.11

Current Limit/Short Circuit Protection

The current limit function determines the maximum output current limit of the rectifier module, regardless of

output voltage or power. Maximum output current is limited to a constant value down to short circuit

condition. Current limiting can be used to mate the rectifier output current ampacity to the needs of the load

and parallel battery to minimize excessive battery recharge current.
The rectifier will sustain a short circuit at the output terminals indefinitely. The maximum short circuit current

shall not exceed 105% of the rated full load current.

2.1.12

Power Limiting

Each rectifier module is designed to limit power output to the module specification. This enables more

current to be supplied at lower output voltages, and allows matching of output to the demand of constant

power loads, normally seen with telecom equipment.
This feature may also be used for a faster recharge of flooded batteries paralleled with the load.

NOTE: Current limiting overrides the power-limiting feature.

2.1.13

High Voltage Shutdown (HVSD)

This feature provides protection to the load from over voltage conditions originating from the rectifiers. It

operates by shutting down the offending rectifier module when a high output voltage condition occurs.

Indication is through the red Alarm (Module Fail) LED. Modules will restart automatically; however, if more

than three over voltage conditions occur in one minute, the module will latch off and remain shut down until

it is reset.

2.1.14

Battery Eliminator Operation

Rectifier modules maintain all specifications (except where indicated) with or without a battery attached in

parallel to the output; however, if a battery or another module supplying DC voltage in parallel is not

present, there will be no monitoring or control activity if there is an AC power failure or input fuse failure.

2.2

Distribution Module

030-834-20 (Cordex CXRF-HP 48-1.2kW center mounting 2RU shelf for systems up to 4800W)
The shelf incorporates a distribution module for DC breaker/fuse output as well as battery connections. The

module includes support for up to four AM plug-in breakers and ten GMT fuse positions. Two battery-

landing positions, a 125A battery shunt, and a site ground are also provided. It may also incorporate an

LVBD.
This module contains a unique sliding connection point system to allow for the several dual-hole lug

terminations in a compact space. See Wiring and Connections chapter of this manual for more details.

Advertising