1 introduction, 1 scope of the manual, 2 product overview – Alpha Technologies Cordex 48-1.2kW User Manual

Page 7: Ntroduction, Scope of the manual, Product overview, 1introduction

Advertising
background image

030-834-J0 Rev A

Page

1 of 34

1

Introduction

1.1

Scope of the Manual

This instruction manual explains the installation, interconnection, and operation of the Alpha Cordex CXRF-

HP 48-1.2 kW 48 Vdc power and distribution systems. Listed below are the four available configurations:
•

1RU shelf system, 3 rectifier modules, with CXCM1 controller and GMT fuse distribution (Figure 1)

•

1RU shelf system, 4 rectifier modules, up to 4800W output power with CXCM1 controller (Figure 2a)

•

1RU shelf system, 5 rectifier modules, up to 6000W bulk power output (Figure 2b)

•

2RU shelf system, 4 rectifier modules, up to 4800W output power, with CXCM1 controller, breakers

and GMT fuses distribution (Figure 3)

NOTE: To aid the user with installation, reference is made to drawings located at the rear of the manual.

1.2

Product Overview

•

Designed specifically for restricted space installations, these 48Vdc power distribution systems

incorporate the HP (High Performance) series of 48V 1.2kW Cordex rectifier modules.

•

Complete front access design, allowing for all customer connections in front of the rack channel.

•

Cordex rectifier modules use a high frequency, switched mode conversion technique to provide a fully

regulated and isolated DC output from the AC mains. The Cordex CXRF-HP 48-1.2kW rectifier model

input is universal to allow use on 120/208/220/240Vac 50/60Hz electrical service.

•

Rectifier power modules are “hot swappable”—they can be inserted or removed from the shelf without

cutting power to or from the system or the load.

•

Additional power modules can be included with the system at the time of ordering or added after the

shelf has been installed.

•

The shelves are designed for horizontal mounting in a 19" or 23" center mount installation via universal

mounting brackets (EIA rack spacing) and utilize dual IEC-type connectors for multiple AC line cord
solutions.

•

The Alpha Cordex CXCM1 was designed as a modular CXC controller for the Cordex CXRF-HP 48-

1.2kW rectifier series. Details for installation and wiring are provided in the respective chapters of this
documentation package.

•

All models of the CXC allow the user to set up, control and monitor the entire power system and

ancillary components from one central, easy-to-use source: your web browser. The CXCM1 model
does not have a touch screen display; therefore, system setup and management is performed

exclusively with the web interface. Details of controller operation are provided in the current version
software manual.

•

The equipment is suitable for installation in Network Telecommunication Facilities.

•

The distribution component uses up to four bullet-type breakers and up to ten GMT fuse positions. The

distribution module also allows for termination of two battery strings and includes a 125A battery shunt.

Advertising