5 wiring and connections, 1 safety precautions, 2 tools required – Alpha Technologies Cordex 48-1.2kW User Manual

Page 23: 3 ac feeder protection/sizing, Iring and, Onnections, Safety precautions, Tools required, Ac feeder protection/sizing, 5wiring and connections

Advertising
background image

030-834-J0 Rev A

Page

17 of 34

5

Wiring and Connections

This chapter provides cabling details and notes on cable sizing for DC applications with respect to the shelf.

NOTE: Refer to the drawings located at the rear of the manual.

5.1

Safety Precautions

WARNING

Hazardous AC voltages may be present. Ensure power at the AC service panel is off before

attempting work on the AC connections. Use a voltmeter to verify the absence of voltage. Clearly

mark the correct polarity of the battery leads before commencing work on DC connections.
Refer to the previous (Installation) chapter for additional safety precautions.

5.2

Tools Required

Various tools are essential for product installation. Insulated tools are recommended. Use this list as a

guide:

Slot head screwdrivers (blade sizes: 1/4", 1/8", 1/16")

Philips head screwdriver, #2 (tip size 3/16")

Digital voltmeter equipped with test leads

Adjustable 24/48Vdc load (optional)

Cutters and wire strippers

Crimping tool (optional for large gauge wire)

Socket and rachet set (Imperial measure)

Anti-static wrist strap

Computer (laptop) with Microsoft Internet Explorer 7 or greater

Crossover cable RJ-45 (for access using the Ethernet port)

5.3

AC Feeder Protection/Sizing

To maximize system reliability, the AC feed divides the rectifiers into groups to be supplied by separate

feeds. See customer connections drawing (modules are numbered left to right).

030-834-20: TBA-1 feeds modules 1 and 2. TBA-2 feeds modules 3 and 4.

030-835-20: TBA-1 feeds modules 1 and 2. TBA-2 feeds modules 3 and 4.

030-845-20: TBA-1 feeds modules 1. TBA-2 feeds modules 2 and 3. TBA-3 feeds modules 4 and 5.

030-851-20: TBA-1 feeds modules 1 and 2. TBA-2 feeds modules 3.

It is recommended, for each feed, to use a dedicated protection feeder breaker located at the AC

distribution panel. The feeder breaker can also act as the disconnect device for the connected modules.

AC Input (Vac)

Number of Rectifiers

on AC Feed

Circuit Breaker

Exact Value to Use (A)

120

2

15

208/220/240

2

20

Table A–Recommended AC supply configuration