Dc output to battteries – Alpha Technologies Cordex 48-1.2kW User Manual

Page 26

Advertising
background image

030-834-J0 Rev A

Page

20 of 34

2.

After the plug-in connector has been removed, attach the cables to the terminal block. Verify the polarity.


3.

Insert the terminal block together with attached cables. Use tie wraps to secure the cables.

4.

Insert fuses into the slots.

The maximum allowable output current of the GMT box is 40 A distributed over up to eight poles. The

bigger left pole can accommodate a current of up to 10 A with a fuse of up to 15 A. The other smaller poles

can each accommodate a current of up to 8 A with a fuse of up to 10 A.
When using fewer than eight poles, space the wire connections evenly to avoid overheating one side of the

GMT box. For example, if you’re using four poles, leave the adjacent positions empty. When using the left

pole with a 15 A fuse, always leave the adjacent position empty.
DC Output to Battteries
The wires must be UL approved XHHW or RHH/RHW (for Canadian users, RW90 Type). Double check the

battery polarity and then connect the positive cable to the top side of the output bar and negative cable to

bottom side.

Attach cables to plug-in connector

Insert plug-in connector with

cables

Secure cables with

tie wraps

Maximum 15-A fuse

Maximum 10-A fuses