6

Operation

6.1

Main Rectifier States

Rectifier operation has five main states; each state is distinct and necessary for the operation of the

rectifier.

Off

Start delay

Soft start

Normal operation

Turning off

6.1.1

Off

The rectifier is in the Off state immediately after power is applied to the rectifier or after a rectifier shutdown

(remote or local shutdown, AC shutdown, OVP or thermal shutdown).
In this state the DC-DC converter is turned off and the CXC monitors its inputs for the proper conditions to

begin the start up sequence.
When the conditions have been met for the rectifier to start up, it transitions to the Start Delay state.

6.1.2

Start Delay

When the rectifier is in the Start Delay state, the DC-DC converter is held off and still not sourcing power,

waiting for a given amount of time before transitioning to the next state.
The CXC continues to monitor its inputs.
After the Start Delay state the rectifier transitions to the Soft Start state.

NOTE: Soft start, or current walk-in, gradually increases the voltage and current output of the rectifier upon startup.

This is done to reduce the instantaneous load on the AC source.

6.1.3

Soft Start

When the Soft Start state is entered, the rectifier is turned on and the output voltage and output current

gradually increased. If a load is present, the rectifier begins to source power.
When the voltage and current limit ramps have finished, the rectifier will transition to the Normal Operation

state.

6.1.4

Normal Operation

The Normal Operation state is the state that the rectifier will be in performing all of the rectifier functions

and features specified herein.
From this state, the only valid transition is to the Turning Off state. This transition will happen if the rectifier

is required to shut down.

6.1.5

Turning Off

The Turning Off state is entered because a short delay is required before the rectifier actually turns off to

take care of any initialization requirements.
When this short delay has elapsed, a transition to the Off state is made.