6.2

Main Rectifier Modes

In addition to main rectifier states, there is a set of main rectifier modes. These modes are divided into two

categories:

6.2.1

Output Voltage Modes

Voltage modes, under software control, can directly adjust the output voltage. Situations, such as the

rectifier being in current limit, can change the output voltage with no software control.
The following table describes the five output voltage modes.

Output Voltage Modes

Active when…

Float

Output voltage is set to the float voltage setting.

Equalize

Output voltage is set to the equalize voltage setting.

Battery Test

Output voltage is set to the battery test voltage setting.

Safe

Output voltage is set to the safe mode voltage setting.

Manual Test

Output voltage can be manually adjusted outside of the standard adjustment

Table C–Output voltage modes

6.2.2

Output Current/Power Modes

These four output current/power modes directly affect the output current and power:

Output Current/Power Mode

Output current and power limit have been reduced due to:

Temperature foldback mode

High temperature of the heatsink or internal ambient temperature sensor.

AC foldback mode

Low AC input voltage.
Note: reduces the risk of tripping an AC breaker due to increased AC
current draw as the AC voltage decreases.

Short circuit foldback mode

Short circuit at the output.

Internal fault foldback mode

Internal fault.

Table D–Output current/power modes

6.3

Can Bus Communications

The CAN bus is used for commands and data transfer between the rectifier and CXC to configure the

rectifier with system settings and to monitor rectifier status.