Hardware specifications, cxcm1, Recommended signal wire sizes (as per ul/csa) – Alpha Technologies Cordex 48-1.2kW User Manual

Page 46

Advertising
background image

Specifications for Alpha CXCM1 Cordex Controller Continued

Alpha Technologies Ltd.

018-598-B1 Rev B

Printed in Canada. © 2010 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved.

Page 2 of 2

Hardware Specifications, CXCM1

CPU:

Coldfire

RAM:

8MB

Flash:

4MB standard

Display:

4 digit LCD

Front Panel Controls:

Display pushbutton toggle switch for voltage (V) or current (A)

Reset switch (soft reset button; hold for 3 seconds to reset IP)

LED’s:

System OK (Green)

Power System Minor Alarm (Yellow)

Power System Major Alarm / Controller Fail (Red)

Audio:

Built-in speaker for alarm and popup message tones

Dimensions:

44mm H x 88mm W x 318mm D

[1.73" H x 3.5" W x 12.5" D]

Weight:

0.62 kg (1.36 lb.)

Mounting:

Modular on Cordex CXRF 48-1.2kW series shelves

[options for 1RU horizontal or 2RU vertical orientation depending on shelf]

Relay Outputs:

Four (4) Form C, 60Vdc 1A maximum

Digital Inputs:

Two (2), 0 to 60Vdc

Analog Inputs:

One (1) DC voltage, 0 to 60Vdc

One (1) DC current, ±50mV

Two (2) temperature, 0 to 20Vdc with power source

Communication Ports:

Ethernet RJ-45, Alpha Modem DB-9, CAN [see shelf specifications]

Recommended Signal Wire Sizes (as per UL/CSA)

Wire Size Range:

#16 to #26 AWG)

(1.5 to 0.14mm

2

)

Temperature Range:

0 to 50°C

(32 to 122°F)

CAUTION – TO REDUCE RISK OF FIRE, USE ONLY #26 AWG (0.14mm

2

) OR LARGER WIRE.

The above information is valid at the time of publication. Consult factory for up-to-date ordering information.

Specifications are subject to change without notice.