Introduction

1.1

Scope of the Manual

This instruction manual explains the installation, interconnection, and operation of the Alpha Cordex CXRF-

HP 48-1.2 kW 48 Vdc power and distribution systems. Listed below are the four available configurations:

1RU shelf system, 3 rectifier modules, with CXCM1 controller and GMT fuse distribution (Figure 1)

1RU shelf system, 4 rectifier modules, up to 4800W output power with CXCM1 controller (Figure 2a)

1RU shelf system, 5 rectifier modules, up to 6000W bulk power output (Figure 2b)

2RU shelf system, 4 rectifier modules, up to 4800W output power, with CXCM1 controller, breakers

and GMT fuses distribution (Figure 3)

NOTE: To aid the user with installation, reference is made to drawings located at the rear of the manual.

1.2

Product Overview

Designed specifically for restricted space installations, these 48Vdc power distribution systems

incorporate the HP (High Performance) series of 48V 1.2kW Cordex rectifier modules.

Complete front access design, allowing for all customer connections in front of the rack channel.

Cordex rectifier modules use a high frequency, switched mode conversion technique to provide a fully

regulated and isolated DC output from the AC mains. The Cordex CXRF-HP 48-1.2kW rectifier model

input is universal to allow use on 120/208/220/240Vac 50/60Hz electrical service.

Rectifier power modules are “hot swappable”—they can be inserted or removed from the shelf without

cutting power to or from the system or the load.

Additional power modules can be included with the system at the time of ordering or added after the

shelf has been installed.

The shelves are designed for horizontal mounting in a 19" or 23" center mount installation via universal

mounting brackets (EIA rack spacing) and utilize dual IEC-type connectors for multiple AC line cord
solutions.

The Alpha Cordex CXCM1 was designed as a modular CXC controller for the Cordex CXRF-HP 48-

1.2kW rectifier series. Details for installation and wiring are provided in the respective chapters of this
documentation package.

All models of the CXC allow the user to set up, control and monitor the entire power system and

ancillary components from one central, easy-to-use source: your web browser. The CXCM1 model
does not have a touch screen display; therefore, system setup and management is performed

exclusively with the web interface. Details of controller operation are provided in the current version
software manual.

The equipment is suitable for installation in Network Telecommunication Facilities.

The distribution component uses up to four bullet-type breakers and up to ten GMT fuse positions. The

distribution module also allows for termination of two battery strings and includes a 125A battery shunt.