Air conditioner/heater factory settings, Enclosure temperature alarms, 4 air conditioner/heater factory settings – Alpha Technologies Te45 User Manual
Page 42: 6 enclosure temperature alarms

Alpha Technologies Ltd.
057-106-C0 Rev D
Burnaby, British Columbia. Telephone: 604 436 5900 Fax: 604 436 1233.
Page 33 of 38
5.4 Air Conditioner/heater factory settings
The air conditioner is programmed with the following factory default settings.
Description
Setting
Cooling system ON temperature
80
F (26.6
C)
Heating system ON temperature
60
F (15.5
C)
HVAC fail alarm (dirty filter, broken condenser, etc.) 300 psi, reset at 225 psi
5.5 EVS (Emergency Ventilation System) factory settings
The EVS thermostat is programmed with the following factory default setting.
EVS thermostat
Setting
EVS ON temperature 45
C (113
F)
5.6 Enclosure temperature alarms
The enclosure compartment thermostat is programmed with the following default factory settings.
Battery compartment thermostat
Setting
High temperature alarm (blue)
45
C (113
F)
Low temperature alarm (red)
-15
C (5
F)