HVAC default settings

Refer to the air conditioner manual for operation and maintenance details.

7.1

Air Conditioner/heater

Description

Setting

Cooling system ON temperature

80

F (26.6

C)

Heating system ON temperature

60

F (15.5

C)

HVAC fail alarm (dirty filter, broken condenser, etc.) 300 psi, reset at 225 psi

7.2

Temperature alarms

Compartment thermostat

Setting

High temperature alarm (blue) 45

C (113

F)

Low temperature alarm (red)

-15

C (5

F)