Converter input cabling (+gnd connection), Converter input cabling (-48v connection), Converter fail alarm – Alpha Technologies CXPS 48-1T 48V Pos Gnd User Manual

Page 32: Locate #18 awg wire with tag #17, Locate #18 awg wire with tag #18, Final steps

Advertising
background image

Argus Technologies Ltd.

053-392-C0 Rev A WC

Printed in Canada. © 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 22 of 31

Figure 12–Connection points and wire routing for +24V input into split tier distribution

Converter Input Cabling (+GND Connection)
Terminate the #6 AWG cable with pre-terminated 1/4”-5/8”C lug (with wire marker #13) to the
+GND input terminal labeled “E2” using hardware supplied with shelf.

Route the un-terminated wire end up behind the CXPS system over the top of the distribution
center.

Cut wire to size, strip cable sheath, and crimp supplied 1/4”-5/8”C lug.

Attach lug to distribution tier return bar. Use the hardware supplied with the CXPS system for
attaching lug.

Converter Input Cabling (-48V Connection)
Terminate the #6 AWG cable with pre-terminated 1/4”-5/8”C lug (with wire marker #14) to the
-48V (hot) input terminal labeled “E1” using hardware supplied with shelf.

Route the un-terminated wire end up behind the CXPS system over the top of the distribution
center.

Cut wire to size, strip cable sheath, and crimp supplied 1/4”-5/8”C lug.

Attach lug to breaker output terminal. Use the hardware supplied with the CXPS system for
attaching lug (reference Figure 12 for breaker locations).

Ensure that converter input breaker is installed on –48V output section (breakers 1 through 8).

Converter output (+24V)
wireway

Converter output (+24V)
wire connection
(jumper bar removed)

5.5.2.2

Converter Fail Alarm

Locate #18 AWG wire with tag #17
Attach end with ring lug to -GND output terminal on converter shelf (E4).
Attach unterminated wire end to TB2-8 “Conv Fail” on alarm connection at rear of CSM02 shelf.

Locate #18 AWG wire with tag #18
Attach unterminated wire end to TB2-7 “Conv Fail” on alarm connection at rear of CSM02 shelf.
Attach other unterminated wire end to TB11-36 “Conv Fail” on internal alarm board with Vista II
UDC (reference Figure 13 for alarm board details as well as -08 connection drawing at rear of
this manual).

5.5.2.3 Final

Steps

Reattach back cover to converter shelf.

Install breakers as needed in 10-position breaker tier for required 24V distribution.

Cable from 24V loads to distribution as required.

Plug in 50A 48V feeder breaker into distribution tier.

Switch 50A feeder breaker to “ON” position to supply power to converter shelf.

Refer to Cordex Controller Software manual for custom alarming options using the two new