Fig. 7-15, connecting the rf drop, Fig. 7-16, system interconnection diagram, 7 connecting the rf drop – Alpha Technologies DSM3 for XM2 - Technical Manual User Manual

Page 63: 8 front panel connections, Fig. 7-16, connecting the rf drop, Fig. 7-17, system interconnection diagram, 0 installation

Advertising
background image

63

745-814-B8-001, Rev. C (03/2014)

Fig. 7-17, System Interconnection Diagram

7.8

Front Panel Connections

Connections

Connections with more

than one power supply

Battery Sense Wire Harness

Refer to Section 8 for part numbers and

wiring options.

C

O

M

S

Y

S

C

O

M

S

Y

S

Generator (ECM)

ECM to SCM Interface

(Alpha P/N 704-709-20)

B

C

A

A

B

Comm Port

System Port

Battery Sense Connections

B

C

A

A

Environmental

Tamper Switch Connector

I/O connection

Ethernet connection

RF connection

7.0 Installation

Connect the RF drop according to the diagram below. The RF drop must have a properly installed ground

block in the power supply enclosure. Recommended downstream RF level is 0 dBmV. Connect any other

front panel connections at this time (e.g. battery strings, tamper switch).

RF Cable

to Headend

Grounded Surge Protector

(See Caution Above)

Fig. 7-16, Connecting the RF Drop

7.7

Connecting the RF Drop

Linked CableUPS

Serial Interface Cards

DSM3 Series in

Primary XM2

AlphaBus Cable

(Alpha P/N 875-190-20 for 6',

21 for 9', 22 for 18', 23 for 35')

Install a grounded surge suppressor (Alpha P/N 162-028-10 or equivalent).

CAUTION!