2.4 Smart Display Setup Menu
The Setup Menu contains the following items:
Top Line (provides additional information)
SET UP MENU
TO MANUAL SCROLL
<ESC> TO ADDL INFO
Second Line (cycles through the following parameters):
Parameter
Default
Range
Minimum
Maximum
FLOAT V/C
2.25
2.1V/Cell
2.35V/Cell
ACCEPT V/C
2.35
2.2V/Cell
2.45V/Cell
TEMP COMP
3mV/Cell/°C
0mV/Cell/°C 5mV/Cell/°C
BATT CAPACITY
100 Ah
0 Ah
1,000 Ah
SELF TEST
OFF
ON
or
OFF
TEST INHIBIT
- -
7 days
7 days
TEST INTERVAL
30 days
0 days
360 days
TEST COUNTDOWN 0 days
0 days
365 days
TEST DURATION
10 minutes
5 minutes
180 minutes
FREQ RANGE
3.0 Hz
1.0 Hz
6.0 Hz
TAP SWITCH
YES
NO
or
YES
PIM OPTION
YES
NO
or
YES
OUTPUT 1
ON
ON
or
OFF
OUTPUT 2
ON
ON
or
OFF
OVER CURR 1
15.0 A
3.0 A
30.0 A
OVER CURR 2
15.0 A
3.0 A
30.0 A
RETRY DELAY
60 seconds
5 seconds
301 seconds
RETRY LIMIT
20
0
40
OVER CURR TOL
3 seconds
1 second
10 seconds
N+1 VALID
NO
NO
or
YES
STANDBY TIME
0 minutes
0 minutes
## minutes
STANDBY EVENTS
0 events
0 events
## events
SET DEFAULTS
NO
NO
or
YES
CODE VER
3.01
XM_ CLASS VER
3
DEVICE ADDRESS
0
0
15
SELECT LANGUAGE
ENGLISH
FRENCH
SPANISH