1 discharge data with constant current, continued – Alpha Technologies AlphaCellTM SMU-C Series User Manual
Page 22

745-680-B11-001, Rev. A
22
SMU-C 12-150
End voltage 5Min
10Min
15Min
30Min
1Hr
3Hr
5Hr
10Hr
20Hr
1.60V
656
408
308
188
109
48.0
29.4
16.0
8.64
1.67V
616
387
296
180
108
46.2
28.7
15.8
8.34
1.70V
564
373
289
163
105
43.1
28.1
15.8
8.21
1.75V
553
361
280
155
99.8
41.7
27.5
15.7
7.99
1.80V
495
345
254
144
93.4
40.0
25.9
15.4
7.78
1.85V
437
329
229
132
87.1
38.6
24.2
15.2
7.56
SMU-C 12-200
End voltage 5Min
10Min
15Min
30Min
1Hr
3Hr
5Hr
10Hr
20Hr
1.60V
700
480
350
210
132
54.6
38.2
21.2
10.5
1.67V
630
438
340
204
132
54.4
37.8
20.9
10.5
1.70V
598
422
328
200
131
54.4
37.8
20.7
10.5
1.75V
532
390
310
196
130
54.0
37.5
20.4
10.5
1.80V
480
362
296
190
128
53.8
37.2
20.0
10.1
1.85V
364
298
256
175
127
53.6
36.9
19.7
9.48
5.1
Discharge Data with Constant Current, continued
Amperage values for each battery model as a function of time and voltage @ 77°F/25°C.