Model k571, Resistive portable load bank, Specifications – Atec Avtron-K571 User Manual

Page 2: Outline drawing

Advertising
background image

22.84

[580.00]

52.66

[1338.00]

62.41

[1585.00]

27.97

[710.40]

SCREENED AIR INTAKE THIS
SIDE AND OPPOSITE SIDE

SCREENED
AIR OUTLET

HINGED
ACCESS
PANEL

RIGID CASTERS

SWIVEL CASTERS

CONTROL
PANEL

5.50

[139.70]

HANDLE

9.75

[247.60]

5.31

[134.80]

SPECIFICATIONS:

RELIABILITY: The rugged load resistor assemblies in

the K571 are cooled by a reliable heavy duty industrial

blower. Avtron’s special air switch protects load resis-

tor elements against loss of cooling air. Full rated

contactors are used for switching all load steps.

INDICATOR LIGHTS: BLOWER ON and AIR FAILURE.

SWITCHES: ON-OFF load control for each load step.

MASTER LOAD ON-OFF control for total load (all

selected steps).

METERS (Optional): Digital volt and ammeter.

COOLING: Self-contained 0.5 HP blower, 120 V, single phase, 60 Hz.

CONTROL POWER: 120 volt, single phase, 60 Hz.

MOBILITY: 4 rubber casters: 2 rigid and 2 swivel with foot operated locks.

ACCESSORIES: Optional canvas protective cover and multi-conductor flexible load cables available.

WEIGHT: Approximately 295 lbs. [133.8 kg]

Model K571

Resistive Portable Load Bank

6255 Halle Drive • Cleveland, Ohio, U.S.A. 44125-4615 • 216.573.7600 • FAX 216.573.5953

www.avtronloadbank.com • [email protected]

Bulletin 271 • Rev. D

OUTLINE DRAWING:

K571 LOAD CAPACITY RATINGS:

Other designs available upon request. Consult Factory.

Volts DC

Amps

Load Steps in Amps

52

900

5, 10, 10, 25, 50, 100, 100, 200, 400

1000

50, 50, 100, 100, 100, 200, 200, 200

28

1000

5, 10, 10, 25, 50, 100, 200, 200, 400

All dimensions are in inches [millimeters]. Specifications subject to change without notice.

Quality System Certified to ISO 9001

Advertising