3 Fluke Corporation 1735 Three-Phase Power Logger

Specifications

General

Display

¼ VGA Graphic Color transmissive displays 30 x 40 Pixel with additional background lighting and adjustable

contrast, text and graphics in color

Quality

Developed, designed and manufactured according to DIN ISO 9001

Memory

4 MB Flash memory, 3.5 MB for logging data

Interface

RS-3 SUB-D socket; 115. k Baud, 8 data bits, no parity, 1 stop bit, firmware updates are possible with the

RS-3 interface (9-pole extension cable)

Sample rate

10.4 kHz

Line frequency

50 Hz or 60 Hz, user-selectable, with automatic synchronization

Power supply

NiMH battery-pack, with ac adapter (15 V to 0 V/0.8 A)

Operation time with battery

Typical > 1 hours with backlight low and > 6 hours with backlight high

Dimensions

40 mm x 180 mm x 110 mm (6.1 in x 4.6 in x .8 in)

Weight

1.7 kg (3.75 lb), including battery

Ambient conditions

Working temperature range

-10 °C to +50 °C (+14 °F to +1 °F)

Storage temperature range

-0 °C to +60 °C (+3 °F to +140 °F)

Operating temperature range

0 °C to +40 °C (+3 °F to +104 °F)

Reference temperature range

3 °C ±  °C

Note: The above terms are defined in European Standards. To calculate the specification at any point in the working temperature range, use the temperature

coefficient below.

Temperature coefficient

± 0.1 % of the measured value per °C from the reference

Intrinsic error

Refers to reference temperature, max. deviation is guaranteed for two years.

Operating error

Refers to operating temperature range, max. deviation is guaranteed for two years

Climatic class

C1 (IEC 654-1) -5 °C to +45 °C (+41 °F to +113 °F), 5 % to 95 % RH, no dew

Housing

Cycoloy shock and scratch proof thermoplast V0-type (non-flammable) with rubber protection holster

EMC

Emission

IEC/EN 6136-1:1997 class B

Immunity

IEC/EN 6136-1:1997

Safety

Safety

IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 

Protection

IP65; EN6059 (refers only to the main housing without the battery compartment)

RMS values are measured with a 0 ms resolution.

V-rms wye measurement

Measuring range

57 V/66 V/110 V/10 V/17 V/0 V/

30 V/40 V/60 V/77 V/347 V/

380 V/400 V/417 V/480 V ac

Intrinsic error

± (0. % of measured value. + 5 digits)

Operating error

± (0.5 % of m. v. + 10 digit)

Resolution

0.1 V

V-rms delta measurement

Measuring range

100 V/115 V/190 V/08 V/0 V/380 V/

400 V/415 V/450 V/480 V/600 V/

660 V/690 V/70 V/830 V ac

Intrinsic error

± (0. % of m. v. + 5 digit)

Operating error

± (0.5 % of m. v. + 10 digit)

Resolution

0.1 V