Atec Megger-Multi-Amp-EPOCH-II User Manual

Epoch-ii, High-current output unit, 1000 va of high current

Advertising
background image

EPOCH-II

®

High-Current Output Unit

1000 VA of high current

Rugged, portable test set

Up to 187 Amperes maximum output

EPOCH-II

High-Current Output Unit

DESCRIPTION

The EPOCH-II

®

is a high-current output unit designed to

be controlled by the PULSAR

®

in combination with the

High-Current Interface Module to produce a rugged,
portable high-current, high-volt/ampere test set.

The EPOCH-II also is designed to be controlled by the
EPOCH-10

®

Relay Test Set.

PULSAR/EPOCH-II or EPOCH-10/EPOCH-II combination
uses microprocessor-based, digitally synthesized sine wave
generators and solid-state regulated power amplifiers to
provide sinusoidal voltage and current outputs with
precise control of the phase-angle relationships.

These combinations will produce accurate test results even
with a fluctuating power source or when testing nonlinear
or highly saturable relays.

An optional IEEE-488 GPIB interface transforms the
EPOCH-10/EPOCH-II combination into a programmable
automatic test system when used with an external
controller or computer. Amplitude and/or phase angle can
be set to desired values, step changed, ramped, or pulsed
to new values.

APPLICATIONS

PULSAR/EPOCH-II or EPOCH-10/EPOCH-II combination is
designed to test both complex protective relays which
require phase-shifting capability and simpler relays,
including all overcurrent relays.

The table above lists the different types of relays by
device numbers, and the different combinations of a
PULSAR or EPOCH-10s and an EPOCH-II required to test
them.

FEATURES AND BENEFITS

Output current source has a 5-minute duty cycle rating
of 1000 volt-amperes.

Four output ranges at 0.01 ampere and two output
ranges at 0.1 ampere are provided.

Tough steel, sealed enclosure provides a high shock
and vibration resistance.

Completely compatible with PULSAR via the High-
Current Interface Module and the EPOCH-10 units.

Device No.

Relay Types

Specify

One EPOCH-II and PULSAR
with High-Current Interface
Module or one EPOCH-10

One EPOCH-II and PULSAR
with Interface Module or two
EPOCH-10s

Instantaneous Overcurrent up
to 187 A at 1000 VA

Directional Overcurrent up to
187 A at 1000 VA

All of the above plus. . .
Differential

Distance
(open-delta)

50

67

87

21

One EPOCH-II and PULSAR
with Interface Modules or
three EPOCH-10s

Distance (wye)

21

Ground Directional
Overcurrent up to 187 A at
1000 VA

67N

Overcurrent up to 187 A at 1000 VA

51

Advertising