Atec Megger-torkel-840-860 User Manual

Page 2

Advertising
background image

Programma

TORKEL 840/860 Battery Load Units

FEATURES AND BENEFITS

■

Batteries can be tested “in service”. TORKEL will adjust

to include the load current in the test parameters.

■

User adjustable alarm and shutdown points to avoid

excessive discharge.

■

No loss of test data in the event of a power loss during

testing.

■

Easily expandable for larger battery banks using TXL

extra load units.

■

Can be used “stand alone” or with a PC running

TORKEL WIN Software.

SPECIFICATIONS

Specifications are valid at nominal input voltage and an ambient

temperature of +25° C, (77° F). Specifications are subject to

change without notice.

Environment

Application field

The instrument is intended for use in high-voltage substations and

industrial environments.

Temperature
Operating

0° C to +40° C (32° F to +104° F)

Storage & transport

-40° C to +70° C (-40° F to +158° F)

Humidity

5% – 95% RH, non-condensing

CE-marking

Safety standards

IEC 61010-1:2001 Incl. national dev. for US

and CAEN 61010-1:2001

EMC standards

EN 61326: 1997+A1:1998+A2:2001

General

Power supply voltage

100 – 240 V AC, 50/60 Hz

Power
consumption (max)

150 W

Protection

Thermal cut-outs, automatic overload

protection

Dimensions
Instrument

210 x 353 x 700 mm (8.3” x 13.9” x 27.6”)

Transport case

265 x 460 x 750 mm (10.4” x 18.1” x 29.5”)

Weight

21.5 kg (47.4 lbs)38 kg (83.8 lbs) with

accessories and transport case.

Display

LCD

Available languages

English, French, German, Spanish, Swedish

Measurement section

Current measurement
Display range

0.0 – 2999 A

Accuracy

±(0.5% of reading +0.2 A)

Resolution

0.1 A

Internal current measurement
Range

0 – 270 A

Input for clamp-on ammeter
Range

0 – 1 V

mV/A-ratio

Software settable, 0.3 to 19.9 mV/A

Input impedance

>1 M

Ω

Voltage measurement
Display range 0.0 – 60 V

Accuracy

±(0.5% of reading +0.1 V)

Resolution

0.1 V

Display range 0.0 – 500 V

Accuracy

±(0.5% of reading +1 V)

Resolution

0.1 V

Time measurement
Accuracy

±0.1% of reading ±1 digit

Load section

Max. battery voltage

288 V DC (TORKEL 840)

480 V DC (TORKEL 860)

Max. current

110 A

Max. power

15 kW

Load patterns

Constant current, constant power, constant

resistance, current or power profile

Current setting

0-110.0 A (2999.9 A)

1

Power setting

0-15.00 kW (299.99 kW)

1

Resistance setting

0.1-2999.8

Ω

Battery voltage range, 4 ranges, selected automatically at

TORKEL 840

start of test

Battery voltage range, 5 ranges, selected automatically at

TORKEL 860

start of test

Stabilization

±(0.5% of reading +0.5 A)

(For internal
current measurement)

Battery

Highest

Resistor

voltage

permissible

element

current

(Nominal values)

Range 1

10 – 27.6 V

110 A

0.165

Ω

Range 2

10 – 55.2 V

110 A

0.275

Ω

Range 3

10 – 144 V

110 A

0.55

Ω

Range 4

10 – 288 V

55 A

3.3

Ω

Range 5

2

10 – 480 V

55 A (max

3.3

Ω

power 15 kW)

1) Maximum value for a system with more than one load unit

2) TORKEL 860

Advertising