Atec Simplex-Swift-E User Manual

Swift-e, Insight, Onsite

Advertising
background image

®

Insight

Onsite

Overview

10kw, 15kw, 20kw

120/240vAC, 2/3-wire, single-phase

250w resolution

Description

Quick and easy testing of small

generators and AC power sources is

possible with the Simplex Swift-e.

Portable, fully self-contained, lightweight

and hand transportable, the Swift-e

can be used to test and maintain small

engine generators:
• Residential standby
• Contractor generators
• Marine generators
• RV generators
• Small wind turbines

The Swift-e is also suitable for other AC

power sources:
• 120/240v panelboards and distribution
• Inverters
• Small UPS

Swift-e’s are available in three versions:
Swift-e: 10kw
Swift-e+: 15kw
Swift-e Ultra: 20kw

All versions are:
• Switchable in 250w steps
• 120/240vAC re-connectable

All control and cooling circuits operate

from the source under test. Digital test

instrumentation and connections cables

are included.

Instrument/Control Panel

Digital Power Meter:
• AC Voltage, 1/2%, + 1 digit
• AC Amperes, 1/2%, + 1 digit
• Frequency, 1/2%. + 1 digit
• KW, 1%, + 2 digits
• Power Factor, 2%, + 2 digits

Master load switch, applies all load

preset with load step toggle switches

Load step toggle switches

Fan/control power toggle switch

Ratings

Swift-e: 10,000 watts, 120/240V AC,

single-phase

Swift-e+: 15,000 watts, 120/240V AC,

single-phase

Swift-e Ultra: 20,000 watts, 120/240V AC,

single-phase

Features

Load elements: Sealed, tubular-

type element consisting of nichrome

resistance wire sealed within an incolloy

sheath (nickel alloy). Electrically dead

exterior of element reduces hazard

of electric shock and short circuit of

elements.

Element is rustproof, vibration and

shock proof.

Swift-e

Portable Load Bank

10kw, 15kw 20kw

Load control: Panel mounted toggle

switches for each load step and master

load control. Main contactor for master

load control/block loading.

Load element circuit protection: Main

circuit breaker with overload/short circuit

trips.

Overtemperature sensor to trip main

contactor and activate alarm indicator.

Overvoltage sensor to protect against

incorrect connection of load bank

(connection of 240V to 120V circuits).

Trips main contactor and activates alarm

indicator.

Connection cable set, 10’, with ring lug

terminations.

NEMA type 1 enclosure, aluminum

construction, powder coated nickel-

metallic. Includes rubber feet,

combination carry handles and cable

wrap.