J.09, Heating and cooling batteries – Atec TTC-2000 User Manual
Page 2

LED indication on the controller when the output is active
Two inputs for NTC sensors, one main sensor and one min/max limit
One input for 0 - 10 V DC control signal
Setpoint : selectable, either internal or external
Function
The controller pulses the entire power output ON/OFF. The controller utilises time-proportional control, the ratio between
On-time and Off-time is varied to fit the prevailling heating requirement (exemple ON = 30s and OFF = 30s gives 50 %
output power).
Settings
Setpoint range : 0 to 30°C, the choice of sensor determines the controller setpoint range
Minimum limit : 0 to 30°C
Maximum limit : 20 to 60°C
Cycle time : 6 to 120 s
Dimensions
(W x H x D) : 160 x 207 x 94 mm
J.09
Heating and
cooling batteries
www.airtradecentre.com
J.09 TTC 2000 2/2 - 2012/8/19 - AA-EN