APC BACK-UPS BR650CI User Manual

Back-ups, Connect battery, Power on

Advertising
background image

1

Connect Battery

For safety, the Back-UPS is shipped with one battery wire disconnected. The Back-UPS will not operate until the wire is connected to the touch safe battery

terminal.

NOTE: Small sparks may occur during battery connection. This is normal.

TURN the Back-UPS over, and slide

the battery compartment cover off of

the battery housing.

1

2

3

REMOVE the battery from the battery

compartment, and connect the black wire

to the negative (-) battery terminal. Ensure

the battery is installed as shown below.

INSTALL the battery compartment cover

back onto the battery housing.

Place the Back-UPS to avoid:

- Direct sunlight
- Excessive heat
- Excessive humidity or contact with fluids

Plug the Back-UPS power cord directly into a wall outlet, and not to a surge
protector or power strip. The wall outlet should be located near the equipment, and
easily accessible.

Power On

Power

Switch

UPS Status Indicator

(Green - OK, Red or Amber-

See User Manual)

Power On

2

Surge Protection Only

These outlets provide full-time protection from surges even if the

Back-UPS is switched OFF. Plug your printer, fax machine,

scanner, or other peripherals that do not need battery power into

these outlets.

Battery Backup

Surge Protection

These outlets are powered whenever the Back-UPS is switched
ON. During a power outage, or other utility problems (brownouts,
over-voltages), these outlets will be powered for a limited time by
the Back-UPS. Plug your computer, monitor, and two other data-
sensitive devices (external disk or tape drive) into these outlets.

3

990-2994B Copyright 2007 American Power Conversion Corp.

All other trademarks are property of their respective owners.

APC, Back-UPS and PowerChute are registered trademarks of American Power Conversion Corp.

Power On

Press the ON/OFF switch to power the unit
ON.

A single short beep, and the green “Power On”
indicator confirms that the Back-UPS is on and
ready to provide protection.

The Back-UPS should charge for at least 24
hours to ensure sufficient runtime. The unit is
being charged whenever it is connected to utility
power, whether the unit is turned ON or OFF.

The Back-UPS ES indicates its operating status using a combination of visual and audible indicators. Use the
following table to identify the status of the Back-UPS ES.

Visual Indications

(Power On - Green)

(Replace Battery - Red)

Audible Indication

(Buzzer)

Condition

GREEN On

Off

Power On - Back-UPS is supplying conditioned utility power to the

connected equipment.

GREEN On (Off during

4 beeps)

4 beeps repeated
every 30 seconds

On-Battery - Back-UPS is supplying battery power to the load

connected to the Battery outlets.

Flashing GREEN

Constant Beeping

(every 1/2 second)

Low Battery Warning - The Back-UPS is supplying battery power to the

load connected to the battery outlets, and the battery has 1.5 minutes of

battery power remaining.

Alternating

GREEN & RED

Constant tone

Bad Battery Detected - Battery needs to be charged, or is at end of life

and must be replaced (see Replace Battery).

Flashing

RED

Constant tone

Battery Disconnected - The battery is disconnected or it is a bad

battery (see Replace Battery).

Off

Short beep every

4 seconds

Low Battery Shutdown

- During On Battery operation the battery

power was almost completely exhausted, and the Back-UPS is waiting

for utility power to return to normal.

Off

Constant Tone

On Battery Overload - Connected equipment requires more power

than provided by Back-UPS battery. Unplug devices one at a time to

remove overload. If not corrected contact APC Technical Support.

GREEN On

Constant Tone

On Line Overload - The power drawn by the connected equipment

exceeds the power capacity of the Battery Backup.

Flashing

RED

Chirp every 2 seconds Charger Warning - Back-UPS has experienced an internal problem, but

continues to power the load. Contact APC Technical Support.

Off

Constant Tone

Charger Fault - Back-UPS has an internal problem, and is no longer

powering the load. Contact APC Technical Support.

Alternating

GREEN/AMBER/RED

Off

Button Program Mode - see Section 4, and the table below.

GREEN Flashing

Off

Low Sensitivity Mode - see Section 4, and the table below.

RED Flashing

Off

Medium Sensitivity Mode - see Section 4, and the table below.

AMBER Flashing

Off

High Sensitivity Mode - see Section 4, and the table below.

Status Indicators

4

Transfer Voltage and
Sensitivity Adjustment

(Optional)

In situations where the Back-UPS, or connected
equipment, appears too sensitive to the input volt-
age, it may be necessary to adjust the transfer
voltage. This is a very simple task that requires
the use of an ON/OFF push button. To adjust the
transfer voltage, perform the following steps:
1. Plug the Back-UPS into the utility power

source. The Back-UPS will be in “Standby
mode” (no indicators are lit).

2. Press the ON/OFF push button fully in for 10

seconds. The Online LED will begin glowing in
a cyclical order: GREEN-AMBER-RED, indi-
cating it is going into “Program mode”.

3. The Back-UPS will then indicate the current

sensitivity, as shown in the Transfer Voltage
and Sensitivity Adjustment
table below.

4. To select the LOW sensitivity setting, press the

ON/OFF push button until the LED begins
flashing GREEN.

5. To select the MEDIUM sensitivity setting,

press the ON/OFF push button until the LED
begins flashing RED.

6. To select the HIGH sensitivity setting, press

the ON/OFF push button until the LED begins
flashing AMBER.

7. To exit Programming mode, once sensitivity is

set, wait approximately 5 seconds, and all of
the LED indicators will be off (unlit).

Connect Equipment

Transfer Voltage and Sensitivity Adjustment

Indicators

Flashing

Sensitivity

Setting

Input Voltage Range

(For Utility Operation)

When to Use

Green

Flashing

LOW

155 - 290

Input voltage is extremely low or high.
Not recommended for computer loads.

Red Flashing

MEDIUM

(factory default)

160 -280

Back-UPS frequently goes on battery.

Amber

Flashing

HIGH

165 - 270

Connected equipment is sensitive to voltage
fluctuations.

Connect AC Line Cord

Plug the Back-UPS power cord into a wall outlet, not a surge
protector or power strip. The outlet should be near the equipment
and easily accessible.

Back-UPS

®

BR650CI / BR650CI-AS

User Guide

Advertising
This manual is related to the following products: