11
www.climacoolcorp.com
Single(combine
withbackǦtoǦback)
EndǦtoǦEnd
ONLY
Single(combine
withendǦtoǦend)
BackǦtoǦBack
833/4
833/4
393/4
Ǧ
84
833/4
1681/2
393/4
801/2
84
1681/2
2531/4
393/4
801/2
84
1681/2
338
393/4
801/2
84
2531/4
4223/4
393/4
801/2
84
2531/4
5071/2
393/4
801/2
84
338
5921/4
393/4
801/2
84
338
677
393/4
801/2
84
4223/4
7613/4
393/4
801/2
84
4223/4
8461/2
393/4
801/2
84
5071/2
9311/4
393/4
801/2
84
5071/2
1016
393/4
801/2
84
2Modules
3Modules
4Modules
5Modules
Height
(inches)
Depth(inches)
Width(inches)
ModelUCA
9Modules
10Modules
11Modules
12Modules
6Modules
1Module
7Modules
8Modules
Notes:
1.
Modular chiller bank width dimensions above include 1” for spacing between modules (Refer to page 12 -
Water Piping Confi guration - Figure 1). Example: 5 modules in an end-to-end confi guration is 422 3/4” wide or
in a back-to back confi guration is 253 1/4” wide and 80 1/2” deep.
2.
When piping more than 5 modules, it is recommended to use reverse return (Refer to page 12 - Water
Piping Confi guration - Figure 2). Example: 7 modules in an end-to-end confi guration is 592 1/4” wide or in a
back-to-back confi guration is 338” wide and 80 1/2” deep.
3.
Maximum water fl ow rates for both evaporator and condenser water header systems in one bank of
modules is 1,000 GPM.
Bank Dimensions