Options and accessories – ClimaCool UCW_H 30, 50, 70, 85 User Manual
Page 40
 
www.climacoolcorp.com
38
Options and Accessories
Motorized or Manual Water Isolation Valves
and Flush Ports
Factory installed water isolation valves and flush ports 
shall provide isolation to the module for maintenance and 
cleaning of evaporator and condenser heat exchangers 
while adjacent modules continue normal operation . Both 
motorized and manual valves include standard ¾” fill and 
flush valves. Note: All Heat Pump configurations require 
motorized valves.
Motorized condenser water valves provide head pressure 
regulation for low entering condenser water temperature 
applications (less than 60°F) . 
Available choices include:
• One each motorized valve for evaporator and
condenser with one each manual valves for the 
evaporator and condenser .
• One each motorized valve for the evaporator and one
each manual valve for the evaporator and two each 
manual valves for the condenser .
• Two each manual valves for the evaporator and
the condenser .
Hot Gas Bypass
Factory installed on both circuits allowing unit operation 
below the minimum step of unloading .
Heat Pump
Factory installed reverse cycle heating and cooling operation 
compatible with boiler/tower or geothermal systems .
Heat Recovery
Factory installed option providing hot water, as high as 
135°F, while simultaneously producing chilled water for the 
chiller system .
Pressure Differential Flow Sensor
Field installed to prevent operation of chiller without 
sufficient water flow to evaporator and condenser.
Manual Strainers
Field installed strainers are external to the chiller bank to 
increase efficiency and ensure long life of the modules. 
A minimum 60 mesh stainless steel screen is required to 
protect both the condenser and evaporator circuit . 
Automatic CS Series Strainer Package
Field installed high quality stainless steel filtration systems 
with minimum 60 mesh stainless steel screens . Available 
options include pressure differential alarm and automatic 
time flush.
OSHPD Certification
Special seismic certification in accordance with 
ICC-ES-AC-156 .
Water Header Bypass
To prevent deadheading the pump, a water header bypass 
may be utilized and is mandatory when using motorized 
valves .
Options available for following: 
• Direct Return:
• Motorized evaporator/condenser water
isolation valves
• Motorized evaporator/manual condenser water
isolation valves
• Reverse Return:
• Motorized evaporator/condenser water
isolation valves
• Motorized evaporator/manual condenser water
isolation valves