Delta Controls DPT-2000 User Manual
Page 22

20 IOM-DPT-A: FEB 2014
DAMPING________
(Setting of the solid temporary suppression of the process variable)
|
\
|
BACK
(Return to Local Menu. If you will confirm this option,
|
|
you will come back to main tree of Local Menu)
|
|
|
|
(Confirm one of the following values time constant across
|
|
longer press button ◙. After parameter confirmation
|
|
transmitter will confirm the party of command by the "DONE")
|
0 [S]
|
2 [S]
|
5 [S]
|
10 [S]
|
30 [S]
|
TRANSFEr_______
(Setting of the current output form)
|
\
|
BACK
(Return to Local Menu. If you will confirm this option,
|
|
you will come back to main tree of Local Menu)
|
|
|
|
(Confirm one of the following characteristics across
|
|
longer press button ◙. After parameter confirmation
|
|
transmitter will confirm the party of command by the "DONE")
|
LINEAR
(Linear)
|
SQRT
(Square root)
|
SQRTX^3
(Square root with X^3)
|
SQRTX^5
(Square root with X^5)
|
SPECIAL
(User’s)
|
SQUARE
(Square)
|
LCD1VARiable____
(Type of the process variable displayed on LCD1)
|
\
|
BACK
(Return to Local Menu. If you will confirm this option,
|
|
you will come back to main tree of Local Menu)
|
|
|
|
(Confirm one of the following option across
|
|
longer press button ◙. After parameter confirmation
|
|
transmitter will confirm the party of command by the "DONE")
|
|
|
CURRENT
(On LCD1 will displayed current value in current loop)
|
|
|
PERCENT
(The percent value output signal will displayed on LCD1)
|