Delta Controls DPT-2000 User Manual

Page 22

Advertising
background image

20 IOM-DPT-A: FEB 2014


DAMPING
________

(Setting of the solid temporary suppression of the process variable)

|

\

|

BACK

(Return to Local Menu. If you will confirm this option,

|

|

you will come back to main tree of Local Menu)

|

|

|

|

(Confirm one of the following values time constant across

|

|

longer press button ◙. After parameter confirmation

|

|

transmitter will confirm the party of command by the "DONE")

|

0 [S]

|

2 [S]

|

5 [S]

|

10 [S]

|

30 [S]

|


TRANSFEr
_______

(Setting of the current output form)

|

\

|

BACK

(Return to Local Menu. If you will confirm this option,

|

|

you will come back to main tree of Local Menu)

|

|

|

|

(Confirm one of the following characteristics across

|

|

longer press button ◙. After parameter confirmation

|

|

transmitter will confirm the party of command by the "DONE")

|

LINEAR

(Linear)

|

SQRT

(Square root)

|

SQRTX^3

(Square root with X^3)

|

SQRTX^5

(Square root with X^5)

|

SPECIAL

(User’s)

|

SQUARE

(Square)

|


LCD1VARiable
____

(Type of the process variable displayed on LCD1)

|

\

|

BACK

(Return to Local Menu. If you will confirm this option,

|

|

you will come back to main tree of Local Menu)

|

|

|

|

(Confirm one of the following option across

|

|

longer press button ◙. After parameter confirmation

|

|

transmitter will confirm the party of command by the "DONE")

|

|

|

CURRENT

(On LCD1 will displayed current value in current loop)

|

|

|

PERCENT

(The percent value output signal will displayed on LCD1)

|